Electrical Connection - GEM eSyStep 543 Operating Instructions Manual

Motorized angle seat globe valve
Table of Contents

Advertisement

8 Electrical connection

8 Electrical connection
Appropriate cable socket/appropriate mating connector
▶ The appropriate connector is included for X1.
8.1 Position of the connectors
X1
8.2 Electrical connection
8.2.1 Connection X1
2
1
3
6
4
5
7-pin plug, Binder, type 693
Pin
1
Uv, 24 V DC supply voltage
2
GND
3
Digital input 1
4
Digital input 2
5
Digital input/output
6
Digital output, IO-Link
7
n.c.
GEMÜ 543 eSyStep
OPEN / CLOSE (Code AE)
Signal name
NOTICE
16 / 68
www.gemu-group.com