SMC Networks ISE20B Operation Manual page 71

Digital pressure switch
Hide thumbs Also See for ISE20B:
Table of Contents

Advertisement

<Operation – With security code input ->
•Locking
(1) Press the
button for 5 seconds or longer in measurement mode. When [oPE] is displayed on the
main display, release the button.
The current setting [LoC] or [UnL] will be displayed on the sub display.
(2) Select the key [LoC] with
•Unlocking
(1) Press the
button for 5 seconds or longer in measurement mode. When [oPE] is displayed on the
main display, release the button.
The current setting [LoC] or [UnL] will be displayed on the sub display.
(2) Select the un-locking [UnL] with
button, then security code is required.
(3) For instructions on how to enter the security code, refer to "How to input and change the security
code" on page 72.
(4) If inputted security code is correct, the indication of the main display changes to [UnL], and pressing
the one of
,
If the security code entered is incorrect, [FAL] will be displayed, and the security code must be entered
again. If the wrong security code is entered 3 times, [LoC] is displayed and the device returns to
measurement mode.
or
button, and press the
or
button. Setting is recognized by pressing the
or
button releases key-lock and the measurement mode returns.
-71-
button to set.
No.PS※※-OMU0006-F