Machine Card And Logbook - Toshiba MMY-MAP0804HT8-E Installation Manual

Hide thumbs Also See for MMY-MAP0804HT8-E:
Table of Contents

Advertisement

SMMS-i
Check code
Indication on 7-segment display on the outdoor unit
Auxiliary code
01: Compressor 1
P07
02: Compressor 2
03: Compressor 3
P10
Detected indoor unit address
P13
01: TS condition
P15
02: TD condition
P17
P18
P19
Detected outdoor unit number
P20
0 *: IGBT circuit
1 *: Position detection circuit error
3 *: Motor lock error
4 *: Motor current detected
P22
C *: TH sensor error
D *: TH sensor error
E *: Inverter DC voltage error
(outdoor unit's fan)
01: Compressor 1
P26
02: Compressor 2
03: Compressor 3
01: Compressor 1
P29
02: Compressor 2
03: Compressor 3
*1PDU number information
01:Compressor 1
02:Compressor 2
03:Compressors 1 and 2
04:Compressor 3
05:Compressors 1 and 3
06:Compressors 2 and 3
07:Compressors 1, 2 and 3
08:Fan
09:Compressor 1 and fan
0A:Compressor 2 and fan
0B:Compressors 1, 2 and fan
0C:Compressor 3 and fan
0D:Compressors 1, 3 and fan
0E:Compressors 2, 3 and fan
0F:Compressors 1, 2, 3, and fan
63-EN
Installation Manual
Check code name
Heat sink overheat error
Indoor overflow error
Outdoor unit flow back error detected
Gas leak detection
Discharge temperature TD2 error
Discharge temperature TD3 error
4-way valve inverse error
High-pressure protective operation
Outdoor fan IPDU error
(NOTE)
Ignore 0-F appearing in the position of "*".
G-TR short protection error
Compressor position detecting circuit error
SMMS-i
12

MACHINE CARD AND LOGBOOK

Machine card
After test run, fill the items on the machine card and paste the card on an accessible place on the product securely before
delivery to the customer.
Describe the following items on the machine card:
name, address and telephone number of the installer, his service department, the service department of the party concerned
or at any addresses and telephone numbers of fire department, police, hospitals and burn centres;
Logbook
Update the log periodically after maintenance as defined in EN378-4.
Describe the following items on the logbook:
1. details of the maintenance and repair works;
2. quantities, kind of (new, reused, recycled) refrigerant which have been charged on each occasion, the quantities
of refrigerant which have been transferred from the system on each occasion (see also EN378-4);
3. if there is an analysis of a reused refrigerant, the results shall be kept in the logbook;
4. source of the reused refrigerant;
5. changes and replacements of components of the system;
6. result of all periodic routine tests;
7. significant periods of non-use.
– 32 –