Toshiba MMY-MAP0804HT8-E Installation Manual page 9

Hide thumbs Also See for MMY-MAP0804HT8-E:
Table of Contents

Advertisement

SMMS-i
• Anchor bolt positions are as shown below:
Continuous hole
(15 x 20 long hole)
Model type
MAP080*, MAP1000*, MAP120*
MAP1404*, 1604*
2. When drawing out the refrigerant pipe from the
underside, set the height of the stand to 500mm or
more.
4. Mount the vibration-proof rubber (including vibration-proof blocks) so that it fits under the whole clamping leg.
GOOD
Install the vibration-proof
rubber so that the bent part
of the fixing leg is
Anchor bolt
grounded.
Vibration-proof rubber
NO GOOD
The bent part of the
fixing leg is not
grounded.
15-EN
Installation Manual
310 or
310 or
more
more
A
A
A
B
A
B
700
990
920
1210
3. Do not use 4 stands on the corner to support the
outdoor unit.
NO GOOD
GOOD
NO GOOD
NO GOOD
SMMS-i
5. Be careful of the connecting arrangement of the header unit and follower units. Set the outdoor units in order of
capacity from the one with the largest capacity. (A (Header unit) ≥ B ≥ C ≥ D)
• Be sure to use a header unit for the leading outdoor unit to be connected to the main pipe. (Figure 1 and 3)
• Be sure to use a T-shaped branch joint (RBM-BT14E/RBM-BT24E: separately purchased) to connect each
outdoor unit.
• Be careful of the direction of the Outdoor unit connection piping kit for the liquid side. (As shown in Figure 2, a
Outdoor unit connection piping kit cannot be attached so that the refrigerant of the main pipe flows directly into
the header unit.)
Liquid piping
(Unit: mm)
▼ Figure 1
GOOD
Header unit
A
GOOD
Main pipe
To the indoor unit
Gas piping
▼ Figure 3
GOOD
Header unit
A
Main pipe
To the indoor unit
• When attaching a Y-shaped branch unit for the gas side, attach it level with the ground (Be sure not to exceed
±15 degrees.). Regarding a T-shape branch joints for the liquid side, there is no restriction for its angle.
A
B
– 8 –
▼ Figure 2
NO GOOD
Follower unit
Follower unit
Header unit
B
C
A
NO GOOD
Main pipe
To the indoor unit
[Inverse connection of a gas-side branch unit]
▼ Figure 4
NO GOOD
Header unit
Follower unit
Follower unit
B
C
A
Main pipe
To the indoor unit
Extension valve
(Horizontal line)
(Horizontal line)
Within ±15 degrees
(A arrow view)
(B arrow view)
At a level position
Installation Manual
Follower unit
Follower unit
B
C
Follower unit
Follower unit
C
B
To gas-side branch
unit
Do not connect
Within ±15
a branch unit
degrees
vertically.
EN
16-EN