Machine Card And Logbook - Toshiba MMY-SUG0801MT8P-E Installation Manual

Hide thumbs Also See for MMY-SUG0801MT8P-E:
Table of Contents

Advertisement

Check code
Indication on 7-segment display on the outdoor unit
Auxiliary code
L30
Detected indoor unit address
P03
01: Compressor 1 side
P04
02: Compressor 2 side
1 : Compressor 1 side
2 : Compressor 2 side
P05
00: Power outage detection
01: Open phase detection
02: Miswiring detection
1 : Compressor 1 side
2 : Compressor 2 side
00: Compressor 1 side or Compressor 2 side
P07
04: Heat sink
P10
Detected indoor unit address
P11
P13
P14
01: Outdoor unit valve is close
01: TS condition
P15
02: TD condition
01:PMV 5 side
P16
02:PMV 6 side
Miss installation of PMV5 and PMV6
P17
0# : 4-way valves
1# : 4-way valve1
P19
2# : 4-way valve2
*Put in outdoor unit No. in [ # ] mark
P20
1 : Fan P.C. board 1
P22
2 : Fan P.C. board 2
1 : Compressor 1 side
P25
2 : Compressor 2 side
1 : Compressor 1 side
P26
2 : Compressor 2 side
11: Compressor 1 side
P29
21: Compressor 2 side
*1 Inverter quantity information
01: Compressor 1 trouble
02: Compressor 2 trouble
03: Compressor 1 and 2 trouble
08: Fan 1 trouble
09: Compressor 1, Fan 1 trouble
0A: Compressor 2, Fan 1 trouble
0B: Compressor 1 and 2, Fan 1 trouble
10: Fan 2 trouble
149-EN
Check code name
External interlock of indoor unit
Discharge temperature TD1 trouble
High-pressure SW system operation
Inverter DC voltage (Vdc) trouble
(compressor) MG-CTT trouble
Power outage detection
Open phase detection
Miswiring detection
Heat sink overheating trouble
Heat sink condensation trouble
Indoor overflow error
Outdoor heat exchanger freezing trouble
Outdoor liquid back flow detection trouble
Another Refrigerant Cycle Protection
Gas leak detection
Injection circuit trouble
Discharge temperature TD2 trouble
4-way valve inverse trouble
High-pressure protective operation
Outdoor fan inverter trouble
Compressor inverter P.C.board trouble
Compressor start up trouble
Compressor position detecting circuit system trouble
A value from 0 to F is displayed in " ".
11: Compressor 1, Fan 2 trouble
12: Compressor 2, Fan 2 trouble
13: Compressor 1 and 2, Fan 2 trouble
18: Fan 1 and 2 trouble
19: Compressor 1, Fan 1 and 2 trouble
1A: Compressor 2, Fan 1 and 2 trouble
1B: Compressor 1 and 2, Fan 1 and 2 trouble
– 75 –
16

Machine card and logbook

Machine card
After test run, fill the items on the machine card and paste the card on an accessible place on the product securely
before delivery to the customer.
Describe the following items on the machine card:
name, address and telephone number of the installer, his service department, the service department of the party
concerned or at any addresses and telephone numbers of fire department, police, hospitals and burn centers;
Logbook
Update the log periodically after maintenance.
Describe the following items on the logbook:
1. details of the maintenance and repair works;
2. quantities, kind of (new, reused, recycled) refrigerant which have been charged on each occasion, the
quantities of refrigerant which have been transferred from the system on each occasion;
3. if there is an analysis of a reused refrigerant, the results shall be kept in the logbook;
4. source of the reused refrigerant;
5. changes and replacements of components of the system;
6. result of all periodic routine tests;
7. significant periods of non-use.