SMMS-i
Adding refrigerant
After finishing vacuuming, exchange the vacuum pump with a refrigerant canister and start additional charging of refrigerant.
Calculation of additional refrigerant charge amount
Refrigerant charge amount at shipment from the factory does not include the refrigerant for pipes at the local site.
For refrigerant to be charged in pipes at the local site, calculate the amount and charge it additionally.
NOTE
If the additional refrigerant amount indicates minus as the result of calculation, use the air conditioner without additional
refrigerant.
Outdoor unit type
Heat pump
type
Charging amount (kg)
Outdoor unit type
Cooling only
type
Charging amount (kg)
Additional refrigerant charge
=
Real length of liquid pipe
amount at local site
Table 1
Liquid pipe dia. (mm)
6.4
Additional refrigerant amount/1m liquid
0.025
pipe (kg/m)
31-EN
Installation Manual
MAP080
MAP100
MAP120
MAP140
11.5
MAP080
MAP100
MAP120
MAP140
10.5
10.5
10.5
11.5
Corrective amount of refrigerant
Additional refrigerant charge
depending on HP of co-
×
+
amount per 1m liquid pipe
operating outdoor units
(Table 1)
(Table 2)
9.5
12.7
15.9
19.1
0.055
0.105
0.160
0.250
SMMS-i
Table 2
Combined HP (HP)
MAP160
Standard type
MAP160
11.5
22.2
0.350
High Efficiency type
Charging of refrigerant
• Keeping the valve of the outdoor unit closed, be sure to charge the liquid refrigerant into the service port at the
liquid side.
• If the specified amount of refrigerant cannot be charged, fully open the valves of the outdoor unit at liquid and
gas sides, operate the air conditioner in COOL mode, and then charge refrigerant into service port at the gas
side. In this time, choke the refrigerant slightly by operating the valve of the canister to charge liquid refrigerant.
• The liquid refrigerant may be charged suddenly, therefore be sure to charge refrigerant gradually.
– 16 –
Combined outdoor units (HP)
8
8HP
10
10HP
12
12HP
14
14HP
16
16HP
18
10HP
8HP
20
10HP
10HP
22
12HP
10HP
24
12HP
12HP
26
16HP
10HP
28
16HP
12HP
30
16HP
14HP
32
16HP
16HP
34
12HP
12HP
10HP
36
12HP
12HP
12HP
38
16HP
12HP
10HP
40
16HP
12HP
12HP
42
16HP
14HP
12HP
44
16HP
16HP
12HP
46
16HP
16HP
14HP
48
16HP
16HP
16HP
16
8HP
8HP
24
8HP
8HP
8HP
26
10HP
8HP
8HP
28
10HP
10HP
8HP
30
10HP
10HP
10HP
32
8HP
8HP
8HP
34
10HP
8HP
8HP
36
10HP
10HP
8HP
38
10HP
10HP
10HP
40
10HP
10HP
10HP
42
12HP
10HP
10HP
44
12HP
12HP
10HP
46
12HP
12HP
12HP
48
12HP
12HP
12HP
Installation Manual
C (Corrective amount
of refrigerant) (kg)
1.5
2.5
3.5
8.5
10.5
0.0
3.0
5.0
7.5
8.5
9.5
11.5
12.5
3.0
4.0
6.0
7.0
8.0
10.0
12.0
14.0
0.0
-4.0
-4.0
-2.0
0.0
8HP
-6.0
8HP
-6.0
8HP
-6.0
8HP
-6.0
10HP
-5.0
10HP
-4.0
10HP
-2.0
10HP
0.0
12HP
2.0
EN
32-EN