Selection Of Installation Place - Toshiba MMY-MAP0804HT8-E Installation Manual

Hide thumbs Also See for MMY-MAP0804HT8-E:
Table of Contents

Advertisement

9-EN
SMMS-i
4

SELECTION OF INSTALLATION PLACE

Upon customer's approval, install the air conditioner in a place which satisfies the following conditions:
• Place where it can be installed horizontally.
• Place which can reserve a sufficient service space for safe maintenance or checks.
• Place where there is no problem even if the drained water overflows.
Avoid the following places:
• Salty places (seaside area) or places with much gas sulfide (hot spring area) (If selecting such a place, special
maintenance is required.)
• Places where oil (including machine oil), steam, oil smoke or corrosive gas is generated.
• Places where an organic solvent is used.
• Chemical plants with a cooling system using liquid carbon dioxide.
• Places where a device generating high frequency (inverter, non-utility generator, medical apparatus, or
communication equipment) is set. (Malfunction or abnormal control of the air conditioner, or interference to
devices listed above may occur.)
• Places where discharged air from the outdoor unit blows against the windows of a neighbour's house.
• Places unable to bear the weight of the unit.
• Places with poor ventilation.
– 5 –
Installation Manual
SMMS-i
Installation space
Leave space necessary for running, installation and servicing.
NOTE
• If there is an obstacle above the outdoor unit, leave a space of 2000mm or more to the top end of the outdoor unit.
• If there is a wall around the outdoor unit, make sure that its height does not exceed 800mm.
Air discharge
Air intake
Air intake
Installation/servicing
surface
Square hole for
handling
Outdoor unit top view
500mm or more
(Rear side)
10mm or more
500mm or more
(Front side)
20mm or more
20mm or more
10-EN
Installation Manual
Air intake
Air intake
10mm or more

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents