Toshiba MMY-MAP0804HT8-E Installation Manual page 15

Hide thumbs Also See for MMY-MAP0804HT8-E:
Table of Contents

Advertisement

SMMS-i
◆ System restriction
Outdoor unit combination
Total capacity of outdoor units
Indoor unit connection
Total capacity of indoor units
(varies depending on the height difference between
indoor units.)
◆ Cautions for installation
• Set the outdoor unit first connected to the bridging pipe to the indoor units as the header unit.
• Install the outdoor units in order of their capacity codes: A (header unit) ≥ B ≥ C ≥ D
• When connecting gas pipes to indoor units, use Y-shaped branching joints to keep pipes level.
• When piping to outdoor units using Outdoor unit connection piping kits, intersect the pipes to the outdoor unit
and those to indoor units at a right angle as shown in figure 1 on "6. INSTALLATION OF THE OUTDOOR UNIT".
Do not connect them as in figure 2 on "6. INSTALLATION OF THE OUTDOOR UNIT".
◆ Allowable length and allowable height difference of refrigerant piping
Item
Total extension of
Less than 96kW
pipe (liquid pipe,
real length)
96kW or more
Farthest piping length L (*1)
Main piping length
Pipe length
Farthest equivalent piping length from the first branch Li
(*1)
Farthest equivalent piping length between outdoor units L0
(*1)
Maximum equivalent piping length of pipes connected to
outdoor units
Maximum real length of pipes connected to indoor units
Maximum equivalent length between branching sections
Height between outdoor and indoor
units H1
Height
difference
Height between indoor units H2
Height between indoor units H3
*1: Farthest outdoor unit from the first branch: (D), farthest indoor unit: (j)
*2: If the total capacity of outdoor units is 46HP or more, make the equivalent length 70m (real length 50m) or less.
*3: Make the difference 65m or less if the height difference between outdoor and indoor units (H1) is more than 3m.
*4: Make the difference 50m or less if the height difference between indoor units (H2) is more than 3m.
*5: Make the difference 30m or less if the height difference between indoor units (H2) is more than 3m.
27-EN
Installation Manual
Up to 4 units
Up to 48 HP
Up to 48 units
H2 ≤ 15m
135% of outdoor units' capacity
15m < H2
105% of outdoor units' capacity
Allowable
Pipes
value
Less than 34HP or
300m
LA + LB + La + Lb + Lc + Ld + L1 + L2 + L3 + L4
less
+ L5 + L6 + L7 + a + b + c + d + e + f + g + h + i + j
34HP or more
500m
Equivalent length
235m
LA + LB + Ld + L1 + L3 + L4 + L5 + L6 + j
Real length
190m
Equivalent length
120m (*2)
L1
Real length
100m (*2)
90m (*3)
L3 + L4 + L5 + L6 + j
25m
LA + LB + Ld (LA + Lb, LA + LB + Lc)
10m
La, Lb, Lc, Ld
30m
a, b, c, d, e, f, g, h, i, j
50m
L2, L3, L4, L5, L6, L7
Upper outdoor
70m (*4)
units
Lower outdoor
40m (*5)
units
40m
5m
SMMS-i
Airtightness test
After the refrigerant piping has been finished, execute an airtight test.
For an airtight test, connect a nitrogen gas canister as shown in the figure on the next page and apply pressure.
• Be sure to apply pressure from the service ports of the packed valves (or ball valves) at the liquid side, gas side
and balance pipe side.
• An airtight test can only be performed at the service ports at the liquid side, gas side and balance pipe side on
header unit.
• Close the valves fully at the gas side, liquid side and balance pipe side. As there is a possibility that the nitrogen
gas will enter into the cycle of outdoor units, re-tighten the valve rods at the liquid side and balance pipe side
before applying pressure.
(When using MAP140 or MAP160, you do not have to re-tighten the liquid side valve rod as their valves at the
liquid side are ball valves.)
• For each refrigerant line, apply pressure gradually in steps at the liquid side, gas side and balance pipe side.
Be sure to apply pressure at the gas side, liquid side, and balance pipe side.
WARNING
Never use oxygen, flammable gases, or noxious gases in an airtight test.
Main piping
Packed valve details
To outdoor unit
To gauge manifold
Liquid-side service port
Gas-side valve
Liquid-side valve
To
Balance
outdoor
To
service port
unit
outdoor
unit
Piping at site
Balance valve
Piping at site
Piping at site
Connected to other follower units
Able to detect a serious leakage
1. Apply pressure 0.3MPa (3.0kg/cm²G) for 5 minutes or more.
2. Apply pressure 1.5MPa (15kg/cm²G) for 5 minutes or more.
Available to detect slow leakage
3. Apply pressure 3.73MPa (38kg/cm²G) for approx. 24 hours.
• If there is no pressure decrease after 24 hours, the test is passed.
– 14 –
Low pressure
gauge
Connected to indoor unit
Gas side valve fully closed
Header outdoor unit
Service port
Brazed
Copper pipe
Fully
closed
Service port
Gas-side
Liquid valve fully closed
service port
Fully
closed
Service port
Balanced pipe side valve
fully closed
Installation Manual
High pressure
gauge
Gauge
V
V
L
H
manifold
Reducing
valve
Copper
pipe
Nitrogen
gas
EN
28-EN

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents