pied.  And the only rationale for implementing this looser require‐
ment would be to avoid superfluous faults.   
 
The Air Alert 96d controller can discriminate between occupied and 
unoccupied duration limits this by making two outlier events (for 30 
minutes and 4 hours) and making the 30 minute event coverage peri‐
od only "Daytime".  The hours of "Daytime" can be set under menu 
function 6.  If occupancy is based on some other criterion than the 
time of day, this binary condition can be accepted into the controller 
system by a digital input channel of a 301ADI.  The event can be made 
conditional on the outlier and the digital input. 
 
Note: The following requirements are from the The 2013 Nonresiden‐
tial Compliance Manual Appendix A form NRCA‐PRC‐03‐F "Enclosed 
Parking Garage Exhaust System Acceptance" 
 
 
Requirement:  Step A 3 instructs "Temporarily override the pro‐
grammed sensor calibration/ replacement period to 5 minutes." 
 
Solution: Reconfigure the time since calibration (TSC) event time limit 
to 0 minutes.  Alternatively, a stale cartridge can be temporarily 
plugged into the E³Point. 
 
 
 
Note that the Air Alert 96d controller/E³Point system reports time 
since calibration in days.  Therefore,  setting the time limit to 5 
minutes would cause an event to activate 1140 minutes (1 day) after 
calibration.   
 
 