The Tests menu provides four main options, divided between two 
screens. Each of these options offers different capabilities. The first 
screen presents three options: 
 
 
Option 
Test sequence 
Start Sim
Sequence 
Maximum load 
 
The second screen option is "Oprt Mode", which offers three separate 
operation settings: Normal, Single Tx or Debug. 
 
 
Setting 
Normal 
Normal controller operation mode 
Single Tx
Activates the polling mode on a single transmitter.
Activates the service mode to perform a calibration and to
Debug 
test Events without triggering actions.
 
 
Enables each output to be activated and validates 
operation of each controller keypad buttons, dis‐
play pixels, and various communication protocols. 
This options starts or stops the Simulation mode, 
which allows a simulation of a gas concentration 
over an associated scale range on all transmitters.  
The simulated gas concentration values are local 
(on the controller) and do not affect logging func‐
tions. (Events will be activated for the simulation 
but detection devices are not affected.) 
Activates all controller components
 
68 
Description 
Description 