Honeywell Air Alert 96d User Manual page 98

Table of Contents

Advertisement

Available languages

Available languages

 
Requirement: Section 120.6(c)7Eiii  "The CO sensor shall be moni‐
tored by a control system.  During occupied periods the system com‐
pares the readings of sensors in the same proximity zone, e.g. if 
the 30 minute rolling average for any sensor in a proximity zone is 
more than 15 ppm above or below the 30 minute rolling average for 
other sensor(s) in that proximity zone, the sensor has failed." 
 
Solution: Create an event to activate if the concentration reading of 
any sensor in a group is an outlier deviating by 15 ppm for longer than 
30 minutes. 
 
 
 
 
Requirement: Section 120.6(c)7Eii  "The CO sensor shall be monitored 
by a control system.  During unoccupied periods the system compares 
the readings of all sensors, e.g. if any sensor is more than 15 ppm 
above or below the average of all sensors for longer than 4 hours, the 
sensor has failed." 
 
Solution:  Configure an event to activate if the concentration reading 
of any sensor in a group is an outlier deviating by 15 ppm for longer 
than 4 hours.   
 
 
 
Note that this requirement is less strict that Section 120.6(c)7Eiii 
above because the aberrant reading is allowed to persist longer.  Thus 
this requirement is only meaningful for garages that are rarely occu‐
98 
 