Scroll through the main Config menu screens using the left (previous) 
or right (next) keypad arrows. 
The third main screen in the Config menu allows the relay configura‐
tion to be set, the AP broadcast mode and to select from four sepa‐
rate manufacturers for the given controller. 
 
 
When Relay Configuration is selected, two further options to config‐
ure the relays are available:  The first screen, Failsafe, appears allow‐
ing  the failsafe to be activated for all relays using the Enter keypad 
button.  This function inverts relay operation to be normally ener‐
gized.  If power is cut, the relay will activate the connected device. (ex. 
a light.) 
  
 
Scrolling to the right displays the "Silence" screen that enables or dis‐
ables the silence option for each relay, using the Enter keypad button. 
 
 
 
 
 
60 