Installation

HVAC Unit Terminations

HVAC unit signals may be up to 28VAC from the equipment terminations.
R
W1 W2
G
Y2
+
24V
DI1
DI2
DI3 OVR T1

Analog Outputs

Connect 4 – 20mA, analog output devices using 18 – 22AWG two-wire twisted, stranded shielded or unshielded wire.
Connected actuators, motors, or drives must be powered separately from the SuperSTAT. If you desire a voltage output,
use an included 500Ω resistor.
R
W1 W2
G
Y2
+
24V
DI1
DI2
DI3 OVR T1

Temperature Inputs

Connect 1000Ω PtRTD temperature sensor inputs (range of –40ºF to 160ºF) using 18AWG two-wire twisted, stranded
shielded wire, maximum 250 ft. length. Sensors can be used for remote zone temperature, return air temperature,
discharge air temperature, or outside air temperature. Sensor wires should be kept at least five feet from live voltage
wiring.
NOTE:
When using remote sensors, the unit may need to be calibrated See the
for more information.
R
W1 W2
G
Y2
+
24V
DI1
DI2
DI3 OVR T1
6
G
A2
A1
A02 A01
GND
T1
T2
T2
T3
T3
G
A2
A1
A02
A01
GND
T1
T2
T2
T3
T3
G
A2
A1
A02 A01
GND
T1
T2
T2
T3
T3
2800 Laura Lane
Middleton, WI 53562
W1 W2
Y1
G
R
Y2
R W1 W2
Y1
Y2
A01
GND
* = Optional
500Ω Resistor
*
+ –
SZ1041 SuperSTAT Configuration Guide
Remote
Discharge
Zone/Return
Air Temp
DI3 OVR T1
T1
T2
T2
|
800.288.9383
|
www.tcsbasys.com
G
Outside
Air Temp
T3
T3