Installation
HVAC Unit Terminations
HVAC unit signals may be up to 28VAC from the equipment terminations.
R
W1 W2
G
Y2
–
+
24V
DI1
DI2
DI3 OVR T1
Analog Outputs
Connect 4 – 20mA, analog output devices using 18 – 22AWG two-wire twisted, stranded shielded or unshielded wire.
Connected actuators, motors, or drives must be powered separately from the SuperSTAT. If you desire a voltage output,
use an included 500Ω resistor.
R
W1 W2
G
Y2
–
+
24V
DI1
DI2
DI3 OVR T1
Temperature Inputs
Connect 1000Ω PtRTD temperature sensor inputs (range of –40ºF to 160ºF) using 18AWG two-wire twisted, stranded
shielded wire, maximum 250 ft. length. Sensors can be used for remote zone temperature, return air temperature,
discharge air temperature, or outside air temperature. Sensor wires should be kept at least five feet from live voltage
wiring.
NOTE:
When using remote sensors, the unit may need to be calibrated See the
for more information.