Optional DDP Supply Fan
Shipping Channel Removal and
Isolator Spring Adjustment

Shipping Tie Down and Isolator Spring

Adjustment

Remove shipping tie down bolt and washer (4—20 to 30
ton, 6—40 to 55 ton, 8—60 to 75 ton). Leave shipping
channels in place. Verify spring height is 0.1" to 0.2"
above shipping channel. Spring height is factory set but
RT-SVX072D-EN
verify and adjust as needed as follows:
1. Back off ALL spring isolator jam nuts (4) at top of
assembly (adjusting one spring effects all others)
2. Turn adjustment bolt (make small adjustments; again
each change effects all other springs. Clockwise raises;
counter clockwise lowers).
3. When correctly adjusted re-tighten jam nuts and
remove shipping channels. Do NOT remove
electrical ground wire strap between isolation base
and unit base.