Trane IntelliPak 1 with Symbio 800 Installation, Operation And Maintenance Manual page 73

Commercial packaged rooftop air conditioners with vav or szvav controls and eflex/edrive
Table of Contents

Advertisement

Figure 47. Supply fan performance with variable frequency drive — 30 ton cooling only, 20/25 ton gas heat- direct
drive plenum, 120% width
8.0
7.5
7.0
6.5
6.0
5.5
5.0
1600 RPM
4.5
1500 RPM
4.0
1400 RPM
3.5
1300 RPM
3.0
1200 RPM
2.5
1100 RPM
2.0
1000 RPM
1.5
1.0
0.5
0.0
0
1000
2000
3000
Important: Maximum static pressure leaving the rooftop is
4.0" H
O positive. The static pressure drops
2
from the supply fan to the space cannot
exceed 4.0" H
RT-SVX072D-EN
2000 RPM
1900 RPM
1800 RPM
1700 RPM
4000
5000
6000
7000
Airflow, CFM
O.
2
2100 RPM
8000
9000
10000
11000
12000
Notes:
Shaded areas represent selectable area.
Contact your local Trane® representative for
more information.
Supply fan performance curve includes internal
resistance of rooftop. For total static pressure
determination, system external static must be
added to appropriate component static
pressure drops (evaporator coil, filters, optional
economizer, optional relief fan, optional heating
system, optional cooling only extended casing,
optional roof curb).
Maximum Cfm (for cULus approval) as follows:
30 ton - 13,500 Cfm.
Minimum motor horsepower is 3 hp. Maximum
motor horsepower is 20 hp. Maximum fan RPM
is 2,100.
Unit Start-up
13000
14000
15000
73