Trane IntelliPak 1 with Symbio 800 Installation, Operation And Maintenance Manual page 144

Commercial packaged rooftop air conditioners with vav or szvav controls and eflex/edrive
Table of Contents

Advertisement

Service and Maintenance
Table 74. Relief/return fan VFD parameters (continued)
Menu
ID
3-02
3-03
3-15
Reference /
3-16
Ramps
3-17
3-41
3-42
4-10
4-12
Limits / Warnings
4-14
4-18
4-19
5-10
Digital In / Out
5-12
5-13
8-30
8-31
8-32
8-33
Communications
8-35
and Operations
8-36
8-01
8-03
8-04
144
Description
Parameter Setting
Minimum Reference
[22] 22 Hz
(HZ)
Maximum Reference
[60] 60 Hz
(HZ)
[11] Local bus reference
Reference 1 Source
[0] No function
Reference 2 Source
[0] No function
Reference 3 Source
Ramp 1 Ramp up Time
[30] 30s
(S)
Ramp 1 Ramp down
[30] 30s
Time (S)
Motor Speed Direction
[0] Clockwise
Motor Speed Low Limit
[22] 22 Hz
[HZ]
Motor Speed High Limit
[60] 60 Hz
(Hz)
Current Limit (%)
[100] 100%
Max Output Frequency
[60] 60 Hz
(Hz)
Terminal 18 Digital Input
[0] No Operation
Terminal 27 Digital Input
[0] No Operation
Terminal 29 Digital Input
[0] No Operation
[2] Modbus RTU
Protocol
[9] = 20T-75T & Unit Model Digit 11= 3, 4, 5, 6, 7, 8
[12] = 20T-75T & Unit Model Digit 11= 9, M, N, P, R, T
Address
[9] = 90T-130T
[7] 115200 Baud
Baud Rate
Parity / Stop Bits
[0] Even Parity,1 Stop Bits
Minimum Response
[0.005] 5ms Min Response Delay Time
Delay (s)
Maximum Response
[0.1] 100ms Max Response Delay Time
Delay (s)
[2] Controlword only
Control Site
Control Timeout Time (s)
[15] 15s
Control Timeout
[2] Stop
Function
RT-SVX072D-EN