Table PD-32 — Supply Fan Performance With VARIABLE FREQUENCY DRIVE or WITHOUT INLET VANES — 20 and 25 Ton
Cfm
Std
.250
Air
RPM
BHP
RPM
4000
370
.34
504
5000
390
.48
514
6000
419
.67
529
7000
451
.92
550
8000
485
1.23
579
9000
520
1.60
609
10000
556
2.05
641
11000
593
2.58
675
Cfm
Std
2.250
Air
RPM
BHP
RPM
4000
1034
3.58
1085
5000
1053
4.09
1106
6000
1061
4.54
1117
7000
1064
5.01
1121
8000
1067
5.57
1123
9000
1072
6.25
1127
10000
1082
7.05
1135
11000
1096
7 .99
1147
Cfm
Std
4.250
Air
RPM
BHP
RPM
4000
1376
7.76
1412
5000
1408
8.78
1445
6000
1433
9.78
1470
7000
1449
10.71
1488
8000
1457
11.58
1498
9000
1461
12.44
1503
10000
1463
13.38
1505
11000
1466
14.46
1507
Notes:
1. Fan performance for 20 and 25 ton rooftops is identical. However, note maximum motor hp size for each size. Contact your local Trane representative for
information on oversized motors.
2. Shaded areas at table extremes note non-standard Bhp or Rpm selection. Contact your local Trane representative for more information.
3. Supply fan performance table includes internal resistance of rooftop. For total static pressure determination, system external static must be added to appropriate
component static pressure drops (evaporator coil, filters, optional economizer, optional exhaust fan, optional heating system, optional cooling only extended
casing, optional roof curb).
4. Maximum Cfm (for UL approval) as follows: 20 Ton — 9,000 Cfm, 25 Ton — 11,000 Cfm
5. Minimum motor horsepower is 3 hp.
6. Maximum motor horsepower as follows: 20 Ton — 15 hp, 25 Ton — 15 hp
7. Maximum 3 hp and 5 hp motor Rpm is 1,100, maximum 7.5 hp to 15 hp motor Rpm is 1655.
8. See RT-EB-104 for further details
44
Performance
Data
.500
.750
BHP
RPM
BHP
RPM
.62
614
.96
707
.80
618
1.16
710
1.03
628
1.43
715
1.32
642
1.76
726
1.68
659
2.15
741
2.13
685
2.63
757
2.65
715
3.22
780
3.25
745
3.89
809
2.500
2.750
BHP
RPM
BHP
RPM
4.06
1132
4.56
1177
4.64
1156
5.20
1203
5.16
1169
5.79
1219
5.67
1175
6.34
1226
6.24
1177
6.94
1228
6.93
1180
7.64
1231
7.76
1186
8.48
1235
8.72
1196
9.47
1243
4.500
4.750
BHP
RPM
BHP
RPM
8.33
1446
8.90
1480
9.41
1480
10.05
1515
10.48
1507
11.18
1542
11.48
1526
12.25
1563
12.41
1538
13.24
1576
13.31
1543
14.20
1582
14.27
1545
15.19
1585
15.37
1547
16.30
1587
(20, 25 Tons)
Total Static Pressure
1.000
1.250
BHP
RPM
BHP
RPM
1.35
788
1.77
859
1.57
793
2.02
867
1.85
795
2.32
869
2.23
802
2.71
873
2.67
814
3.20
882
3.17
829
3.77
895
3.78
845
4.39
910
4.51
867
5.13
926
Total Static Pressure
3.000
3.250
BHP
RPM
BHP
RPM
5.07
1220
5.58
1261
5.78
1247
6.36
1290
6.43
1265
7.08
1310
7.04
1274
7.75
1321
7.66
1278
8.41
1325
8.38
1280
9.15
1327
9.24
1284
10.02
1330
10.24
1290
11.04
1336
Total Static Pressure
5.000
5.250
BHP
RPM
BHP
RPM
9.49
1513
10.08
1545
10.70
1548
11.35
1581
11.89
1577
12.61
1610
13.03
1599
13.82
1633
14.09
1613
14.95
1649
15.10
1620
16.01
16.12
1624
17.08
17 .25
1626
18.22
1.500
1.750
BHP
RPM
BHP
RPM
2.20
922
2.65
980
2.51
934
3.02
996
2.83
938
3.37
1002
3.24
940
3.80
1004
3.75
946
4.32
1008
4.36
957
4.97
1015
5.05
971
5.71
1028
5.80
986
6.53
1043
3.500
3.750
BHP
RPM
BHP
RPM
6.11
1301
6.65
1339
6.95
1331
7.55
1370
7.74
1353
8.42
1393
8.47
1365
9.21
1408
9.18
1371
9.96
1415
9.94
1373
10.75
1418
10.82
1376
11.65
1420
11.86
1380
12.70
1423
5.500
5.750
BHP
RPM
BHP
RPM
10.69
1576
11.30
1606
12.02
1613
12.69
1644
13.34
1643
14.07
14.62
15.81
RT -PRC010-EN
2.000
BHP
3.11
3.54
3.95
4.39
4.93
5.59
6.38
7 .26
4.000
BHP
7.20
8.16
9.09
9.96
10.77
11.59
12.50
13.57
6.000
BHP
11.92
13.37