Table PD-32 — Supply Fan Performance With VARIABLE FREQUENCY DRIVE or WITHOUT INLET VANES — 20 and 25 Ton
Cfm
Std
.250
Air
RPM
BHP
RPM
4000
370
.34
504
5000
390
.48
514
6000
419
.67
529
7000
451
.92
550
8000
485
1.23
579
9000
520
1.60
609
10000
556
2.05
641
11000
593
2.58
675
Cfm
Std
2.250
Air
RPM
BHP
RPM
4000
1034
3.58
1085
5000
1053
4.09
1106
6000
1061
4.54
1117
7000
1064
5.01
1121
8000
1067
5.57
1123
9000
1072
6.25
1127
10000
1082
7.05
1135
11000
1096
7 .99
1147
Cfm
Std
4.250
Air
RPM
BHP
RPM
4000
1376
7.76
1412
5000
1408
8.78
1445
6000
1433
9.78
1470
7000
1449
10.71
1488
8000
1457
11.58
1498
9000
1461
12.44
1503
10000
1463
13.38
1505
11000
1466
14.46
1507
Notes:
1. Fan performance for 20 and 25 ton rooftops is identical. However, note maximum motor hp size for each size. Contact your local Trane representative for
information on oversized motors.
2. Shaded areas at table extremes note non-standard Bhp or Rpm selection. Contact your local Trane representative for more information.
3. Supply fan performance table includes internal resistance of rooftop. For total static pressure determination, system external static must be added to appropriate