3.3.2

Wire treatment

• For the control circuit wiring except for terminals related to the encoder, strip off the sheath of a cable and use as it is.
• Untwist the shielded twisted pair cables after stripping its sheath. Also, treat the shielding wires of the shielded twisted pair
cable to ensure that they will not contact conductive areas.
• Strip the signal wires as follows. If too much of the wire is stripped, a short circuit may occur with neighboring wires. If not
enough of the wire is stripped, wires may become loose and fall out. Twist the stripped end of wires to prevent them from
fraying. Do not solder them. Use a crimp terminal as necessary.
Wire strip length
Terminal name
L (mm)
A, B, C
6
Other than the above
5
Recommended wire gauge: 0.75 mm
Shield(perform protective treatment)
Sheath
Shielded twisted pair cable
L mm
2
3
35