Mitsubishi Electric 800 Series Instruction Manual page 16

Vector control terminal block
Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

Terminal
Function
Common
symbol
SD (sink
(negative
Contact
common))
RES
input
PC (source
(positive
common))
Terminal name
Terminal function description
Use this signal to reset a fault output provided
when a protective function is activated. Turn ON
the RES signal for 0.1 s or longer, then turn it
OFF.
In the initial setting, reset is always enabled. By
Reset
setting Pr.75 , reset can be enabled only at an
inverter fault occurrence. The inverter recovers
about 1 s after the reset is released.
The function of terminal can be changed with
Pr.189 (Input terminal function selection).
PRE-OPERATION INSTRUCTIONS
Rated
specification
Input resistance:
4.7 kΩ
Voltage when
contacts are open:
21 to 27 VDC
When contacts are
1
short-circuited: 4 to
6 mADC
15