Mitsubishi Electric 800 Series Instruction Manual page 19

Vector control terminal block
Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

Terminal
Function
symbol
Encoder
PG
signal
SD
External
power
+24
supply input
*1
Set Pr.73, Pr.267, and the voltage/current input switch correctly, then input an analog signal in accordance with the setting. (Refer to the
Instruction Manual (Detailed) of the inverter.)
Applying a voltage with the voltage/current input switch ON (current input is selected) or a current with the switch OFF (voltage input is
selected) could cause component damage of the inverter or analog circuits of output devices.
18
PRE-OPERATION INSTRUCTIONS
Common
Terminal name
Encoder power
supply terminal
(positive side)
24 V external
power supply input
Terminal function description
Input power for the encoder power supply.
Connect the external power supply (5 V, 12 V, 15
V) and the encoder power cable. When the
encoder output is the differential line driver type,
only 5 V can be input. Make sure the voltage of
the external power supply the same as the
encoder output voltage. (Check the encoder
specification.)
Short terminals PG24 and PG for using the 24
VDC power supply of the FR-A8TP.
For connecting a 24 V external power supply.
If a 24 V external power supply is connected,
power is supplied to the control circuit while the
main power circuit is OFF.
Rated
specification
Input voltage: 23 to
25.5 VDC
Input current: 1.4 A
or less