Gas Rate Cubic Feet Per Hour; Gas Heat Stages; Gas Heat Limit Control Settings - York ZV-06 Installation Manual

Table of Contents

Advertisement

5567611-BIM-B-1218
Table 29: Gas rate cubic feet per hour
Seconds for
One Rev.
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
44
46
48
50
52
54
56
58
60
Calculating the cubic feet of gas consumed per hour
1.
To find the BTU input, multiply the number of cubic feet of
gas consumed per hour by the BTU content of the gas in
your particular locality.
Note: The BTU content of gas varies widely from area to
area, contact your gas company for this information.
By actual measurement, it takes 46 seconds for the hand
on a 1 cubic foot dial to make a revolution with a 80,000
BTU/h furnace running.
2.
To determine rotations per minute, divide 60 by 46 = 1.30.
To calculate rotations per hour, multiply 1.30  60 = 78.
3.
Multiply 78  1 (0.5 if using a 1/2 cubic foot dial) = 78.
4.
Multiply 78  (the BTU rating of the gas). For this example,
5.
assume the gas has a BTU rating of 1050 BTU/ft.
The result of 81,900 BTU/h is within 5% of the 80,000 BTU/h
rating of the furnace.
Adjusting the manifold gas pressure
This gas furnace has two heat stages. The gas valve has two
adjustment screws located under a plastic protective cover. The
second stage (100% input) adjustment screw is adjacent to the
HI marking on the valve. The first stage (60% input) adjustment
screw is located adjacent to the LO marking on the valve (see
Figure 32).
Adjust the second stage (100% input) pressure first, then adjust
first stage (60% input) pressure.
68
Size of Test Dial
1/2 cu. ft.
1 cu. ft.
180
360
150
300
129
257
113
225
100
200
90
180
82
164
75
150
69
138
64
129
60
120
56
113
53
106
50
100
47
95
45
90
43
86
41
82
39
78
37
75
36
72
35
69
34
67
32
64
31
62
30
60
3
1.
Turn off electrical power to the unit.
2.
Using the outlet pressure port on the gas valve, connect a
manometer to monitor the manifold pressure.
3.
Remove the plastic cap that covers the HI and LO pressure
adjustment screws.
4.
Turn on electrical power to the unit.
5.
Set the thermostat to call for second stage heat and start
the furnace.
6.
If necessary, use a screwdriver to turn the second stage
adjustment screw clockwise to increase manifold pressure
or counterclockwise to decrease manifold pressure.
Note: Do not to over-fire the unit on second stage.
7.
After you check the high manifold pressure, adjust the
thermostat to call for first stage heat.
8.
If necessary, use a screwdriver to turn the first stage
adjustment screw clockwise to increase manifold pressure
or counterclockwise to decrease manifold pressure.
Note: Do not to under-fire the unit on first stage.
9.
After you check the pressure, replace the plastic cap
covering the HI and LO pressure adjustment screws.
Note: When using natural gas, the manifold pressure for
second stage (100% input) is 3.5 IWG ± 0.3. The
manifold pressure for first stage (60% input) when
using natural gas is 1.5 IWG ± 0.3.
Table 30: Gas heat stages
Unit
-06, -07, -08, -
10, -12
Table 31: Gas heat limit control settings
Unit
Size
Option
N12
-06
N18
N12
-07
N18
N12
-08
N18
N18
-10
.
N24
N18
-12
N24
1. Roll-out = 300°F, Auxiliary limit = 200°F
Adjusting the temperature rise
The temperature rise is the difference of temperature between
the return air and the heated air from the furnace. The
temperature rise must lie within the range shown on the CSA
rating plate and the data in Table 13.
1.
After about 20 minutes of operation, determine the furnace
temperature rise. Take readings of both the return air and
the heated air in the ducts (about 6 feet from the furnace)
where they are not affected by radiant heat.
No. of burner
1st stage input
tubes
(100% BTU/h)
4
120,000
6
180,000
8
240,000
Main limit setting °F
165
165
165
165
215
195
195
160
195
160
Johnson Controls Ducted Systems
2nd stage input
(60% BTU/h)
72,000
108,000
144,000
1

Advertisement

Table of Contents
loading

This manual is also suitable for:

Zv seriesZv-07Zv-08Zv-10Zv-12

Table of Contents