York ZV-06 Installation Manual page 31

Table of Contents

Advertisement

ZV-06 through -12 high static indoor blower - with powered convenience outlet
Compressors (each)
Size
RLA
LRA
Volt
(tons)
C1
C2
C1
208 11.6 11.6
73
-06
230 11.6 11.6
73
(6.5)
460
5.7
5.7
38
208 11.6
14
73
-07
230 11.6
14
73
(7.5)
460
5.7
6.4
38
208
14
14
83.1 83.1
-08
230
14
14
83.1 83.1
(8.5)
460
6.4
6.4
41
208 16.2 16.2 110 110
-10
230 16.2 16.2 110 110
(10)
460
7.6
7.6
52
Johnson Controls Ducted Systems
OD fan
Supply
motors
blower
MCC
(each)
motor
C2
C1
C2
FLA
FLA
73
18
18
3.5
6.8
73
18
18
3.5
6.8
38
9
9
1.6
3.4
83.1
18
22
3.5
9.6
83.1
18
22
3.5
9.6
41
9
10
1.6
4.7
22
22
3.5
9.6
22
22
3.5
9.6
41
10
10
1.6
4.7
25
25
3.5
9.6
25
25
3.5
9.6
52
12
12
1.6
4.7
Pwr
Pwr
exh.
conv.
Electric heat option
motor
outlet
FLA
FLA
Model
kW
Stages Amps
None
-
E09
6.8
5.5
20
E18
13.5
E24
18
E36
25.5
None
-
E09
9
5.5
20
E18
18
E24
24
E36
34
None
-
E09
9
2.2
20
E18
18
E24
24
E36
34
None
-
E09
6.8
5.5
20
E18
13.5
E24
18
E36
25.5
None
-
E09
9
5.5
20
E18
18
E24
24
E36
34
None
-
E09
9
2.2
20
E18
18
E24
24
E36
34
None
-
E09
6.8
5.5
20
E18
13.5
E24
18
E36
25.5
None
-
E09
9
5.5
20
E18
18
E24
24
E36
34
None
-
E09
9
2.2
20
E18
18
E24
24
E36
34
None
-
E18
13.5
5.5
20
E24
18
E36
25.5
E54
40.6
None
-
E18
18
5.5
20
E24
24
E36
34
E54
54
None
-
E18
18
2.2
20
E24
24
E36
34
E54
54
5567611-BIM-B-1218
1
MCA
1
MCA
with pwr
(amps)
exhaust
(amps)
-
-
56.9
62.4
1
18.9
56.9
62.4
2
37.5
67.9
74.8
2
50
83.5
90.4
2
70.8
109.5
116.4
-
-
56.9
62.4
1
21.7
56.9
62.4
2
43.3
75.1
82
2
57.7
93.1
100
2
81.8
123.3
130.1
-
-
27.6
29.8
1
10.8
27.6
29.8
2
21.7
37.6
40.4
2
28.9
46.6
49.4
2
40.9
61.6
64.4
-
-
62.7
68.2
1
18.9
62.7
68.2
2
37.5
71.4
78.3
2
50
87
93.9
2
70.8
113
119.9
-
-
62.7
68.2
1
21.7
62.7
68.2
2
43.3
78.6
85.5
2
57.7
96.6
103.5
2
81.8
126.8
133.6
-
-
29.8
32
1
10.8
29.8
32
2
21.7
39.3
42
2
28.9
48.3
51
2
40.9
63.3
66
-
-
65.1
70.6
1
18.9
65.1
70.6
2
37.5
71.4
78.3
2
50
87
93.9
2
70.8
113
119.9
-
-
65.1
70.6
1
21.7
65.1
70.6
2
43.3
78.6
85.5
2
57.7
96.6
103.5
2
81.8
126.8
133.6
-
-
30.5
32.7
1
10.8
30.5
32.7
2
21.7
39.3
42
2
28.9
48.3
51
2
40.9
63.3
66
-
-
70.1
75.6
2
37.5
71.4
78.3
2
50
87
93.9
2
70.8
113
119.9
2
112.7
165.4
172.3
-
-
70.1
75.6
2
43.3
78.6
85.5
2
57.7
96.6
103.5
2
81.8
126.8
133.6
2
129.9
154.4
161.3
-
-
33.2
35.4
2
21.7
39.3
42
2
28.9
48.3
51
2
40.9
63.3
66
2
65
77.1
79.9
2
Max fuse
/
2
Max fuse
/
3
breaker
3
breaker
size with
size
pwr exh.
(amps)
(amps)
60
70
60
70
70
80
90
100
110
125
60
70
60
70
80
90
100
100
125
150
30
35
30
35
40
45
50
50
70
70
70
80
70
80
80
80
90
100
125
125
70
80
70
80
80
90
100
110
150
150
35
35
35
35
40
45
50
60
70
70
70
80
70
80
80
80
90
100
125
125
70
80
70
80
80
90
100
110
150
150
35
35
35
35
40
45
50
60
70
70
80
90
80
90
90
100
125
125
175
175
80
90
80
90
100
110
150
150
175
175
40
40
40
45
50
60
70
70
90
90
31

Advertisement

Table of Contents
loading

This manual is also suitable for:

Zv seriesZv-07Zv-08Zv-10Zv-12

Table of Contents