York ZV-06 Installation Manual page 29

Table of Contents

Advertisement

ZV-06 through -12 standard indoor blower - with powered convenience outlet
Compressors (each)
Size
RLA
LRA
Volt
(tons)
C1
C2
C1
208 11.6 11.6
73
-06
230 11.6 11.6
73
(6.5)
460
5.7
5.7
38
208 11.6
14
73
-07
230 11.6
14
73
(7.5)
460
5.7
6.4
38
208
14
14
83.1 83.1
-08
230
14
14
83.1 83.1
(8.5)
460
6.4
6.4
41
208 16.2 16.2 110
-10
230 16.2 16.2 110
(10)
460
7.6
7.6
52
Johnson Controls Ducted Systems
OD fan
Supply
motors
blower
MCC
(each)
motor
C2
C1
C2
FLA
FLA
73
18
18
3.5
5.2
73
18
18
3.5
5.2
38
9
9
1.6
2.6
83.1
18
22
3.5
5.2
83.1
18
22
3.5
5.2
41
9
10
1.6
2.6
22
22
3.5
6.8
22
22
3.5
6.8
41
10
10
1.6
3.4
110
25
25
3.5
6.8
110
25
25
3.5
6.8
52
12
12
1.6
3.4
Pwr
Pwr
exh.
conv.
Electric heat option
motor
outlet
FLA
FLA
Model
kW
None
-
E09
6.8
5.5
20
E18
13.5
E24
18
E36
25.5
None
-
E09
9
5.5
20
E18
18
E24
24
E36
34
None
-
E09
9
2.2
20
E18
18
E24
24
E36
34
None
-
E09
6.8
5.5
20
E18
13.5
E24
18
E36
25.5
None
-
E09
9
5.5
20
E18
18
E24
24
E36
34
None
-
E09
9
2.2
20
E18
18
E24
24
E36
34
None
-
E09
6.8
5.5
20
E18
13.5
E24
18
E36
25.5
None
-
E09
9
5.5
20
E18
18
E24
24
E36
34
None
-
E09
9
2.2
20
E18
18
E24
24
E36
34
None
-
E18
13.5
5.5
20
E24
18
E36
25.5
E54
40.6
None
-
E18
18
5.5
20
E24
24
E36
34
E54
54
None
-
E18
18
2.2
20
E24
24
E36
34
E54
54
MCA
1
MCA
with pwr
(amps)
exhaust
(amps)
Stages Amps
-
-
55.3
60.8
1
18.9
55.3
60.8
2
37.5
65.9
72.8
2
50
81.5
88.4
2
70.8
107.5
114.4
-
-
55.3
60.8
1
21.7
55.3
60.8
2
43.3
73.1
80
2
57.7
91.1
98
2
81.8
121.3
128.1
-
-
26.8
29
1
10.8
26.8
29
2
21.7
36.6
39.4
2
28.9
45.6
48.4
2
40.9
60.6
63.4
-
-
58.3
63.8
1
18.9
58.3
63.8
2
37.5
65.9
72.8
2
50
81.5
88.4
2
70.8
107.5
114.4
-
-
58.3
63.8
1
21.7
58.3
63.8
2
43.3
73.1
80
2
57.7
91.1
98
2
81.8
121.3
128.1
-
-
27.7
29.9
1
10.8
27.7
29.9
2
21.7
36.6
39.4
2
28.9
45.6
48.4
2
40.9
60.6
63.4
-
-
62.3
67.8
1
18.9
62.3
67.8
2
37.5
67.9
74.8
2
50
83.5
90.4
2
70.8
109.5
116.4
-
-
62.3
67.8
1
21.7
62.3
67.8
2
43.3
75.1
82
2
57.7
93.1
100
2
81.8
123.3
130.1
-
-
29.2
31.4
1
10.8
29.2
31.4
2
21.7
37.6
40.4
2
28.9
46.6
49.4
2
40.9
61.6
64.4
-
-
67.3
72.8
2
37.5
67.9
74.8
2
50
83.5
90.4
2
70.8
109.5
116.4
2
112.7
161.9
168.8
-
-
67.3
72.8
2
43.3
75.1
82
2
57.7
93.1
100
2
81.8
123.3
130.1
2
129.9
150.9
157.8
-
-
31.9
34.1
2
21.7
37.6
40.4
2
28.9
46.6
49.4
2
40.9
61.6
64.4
2
65
75.5
78.3
5567611-BIM-B-1218
2
Max
Max fuse
/
1
2
3
fuse
/
breaker
3
breaker
size with
size
pwr exh.
(amps)
(amps)
60
70
60
70
70
80
90
90
110
125
60
70
60
70
80
80
100
100
125
150
30
30
30
30
40
40
50
50
70
70
70
70
70
70
70
80
90
90
110
125
70
70
70
70
80
80
100
100
125
150
30
35
30
35
40
40
50
50
70
70
70
80
70
80
70
80
90
100
110
125
70
80
70
80
80
90
100
100
125
150
35
35
35
35
40
45
50
50
70
70
80
80
80
80
90
100
110
125
175
175
80
80
80
90
100
100
125
150
175
175
35
40
40
45
50
50
70
70
80
90
29