York ZV-06 Installation Manual page 28

Table of Contents

Advertisement

5567611-BIM-B-1218
ZV-06 through -12 high static indoor blower - without powered convenience outlet (Continued)
Compressors (each)
Size
RLA
LRA
Volt
(tons)
C1
C2
C1
208 17.6 17.6 136
-12
230 17.6 17.6 136
(12.5)
460
8.5
8.5
66.1 66.1
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
28
OD fan
Supply
motors
blower
MCC
(each)
motor
C2
C1
C2
FLA
FLA
136
27
27
3.5
14
136
27
27
3.5
14
13
13
1.6
6.6
Pwr
Pwr
exh.
conv.
Electric heat option
motor
outlet
FLA
FLA
Model
kW
None
-
E18
13.5
5.5
E24
18
E36
25.5
E54
40.6
None
-
E18
18
5.5
E24
24
E36
34
E54
54
None
-
E18
18
2.2
E24
24
E36
34
E54
54
MCA
1
MCA
with pwr
(amps)
exhaust
(amps)
Stages Amps
-
-
67.6
73.1
2
37.5
67.6
73.1
2
50
80
86.9
2
70.8
106
112.9
2
112.7
158.4
165.3
-
-
67.6
73.1
2
43.3
71.6
78.5
2
57.7
89.6
96.5
2
81.8
119.8
126.6
2
129.9
147.4
154.3
-
-
32.1
34.3
2
21.7
35.4
38.1
2
28.9
44.4
47.1
2
40.9
59.4
62.1
2
65
73.3
76
Johnson Controls Ducted Systems
2
Max fuse
/
1
2
Max fuse
/
3
breaker
3
breaker
size with
size
pwr exh.
(amps)
(amps)
80
90
80
90
80
90
110
125
175
175
80
90
80
90
90
100
125
150
175
175
40
40
40
40
45
50
60
70
80
90