Led Indicator Status; Manual Testing - Cooper SELHP100R3 Installation Instructions Manual

Emergency light
Table of Contents

Advertisement

Available languages

Available languages

Installation Instructions – Sure-Lites SELHP100R3 / SELHP100R3SD Emergency Light
Instruction for Self-Diagnostic Test:
Once the unit is properly installed according to the installation instruction sheet and AC power supplied, the dual color
LED indicator will come ON and the self-diagnostic test function will automatically initiate. The Unit will switch into a load
calibrating mode for 5-10 seconds to record the connected load. Lampheads will turn ON during this step. Once done, the
LED indicator will show a RED/GREEN flashing status. This indicates that the unit is in Hi-Charge mode. A STEADY GREEN
LED indicates normal service; FLASHING GREEN indicates the unit is testing; GREEN/RED FLASHING indicates the battery
is charging; RED (in different combinations) would indicate a service alert. Refer to the SERVICE INDICATION chart below for
more details. The LED indicator will be OFF when the unit is in emergency mode.
During a manually-initiated test OR monthly/annual self-diagnostic test, if the calibrated load is not detected, then the LED
indicator will flash FOUR times, indicating a load failure error. This error code can be reset by pressing and holding the test
switch for at least (6) seconds, allowing the unit to calibrate the load again.
Self-Diagnostic Service
The self-diagnostic function is factory preset and performs the following:
a.
Monitoring of battery, battery charger, and lamps (both local and remote lamps when applicable )
b.
Self-testing and a 30-second or longer discharge once every 30 days, after AC power has been supplied for a minimum
of 24 hours.
c.
Self-testing and a 30 -minute or longer discharge once every 180 days, after AC power has been supplied for a minimum
of 24 hours.
d.
Self-testing and a 90-minute discharge once every 365 days, after AC power has been supplied for a minimum of 24 hours.
Service Indication
LED Indicator
One flash Red
Two flash Red
Four flash Red
Steady Red
Solid Green
Flashing Green
Red/Green Flashing

Manual Testing

The unit can be manually tested by pushing the test button in the specific patterns listed in the table below.
Action
Push test button One Time (within 2 seconds)
Push test button Two Times (within 2 seconds)
Push test button Three times (within 2 seconds)
Push test button and hold for 3 seconds (While in test
mode)
Push test button and hold for 6 seconds
(While in test mode)
Warning:
a) Make sure that power is OFF before making any electrical connections.
b) Unused wires must be capped using enclosed wire nuts.
4
COOPER LIGHTING SOLUTIONS

LED Indicator Status

Circuit Fault
Battery Fault
Lamp or Load Fault
Battery Disconnected
Trickle Charge
Test Mode
Hi-Charge
IB50533722
Installation Instructions
Reaction & LED Indication
30-second test: FLASHING Green
30-minute test: Green FLASHING twice
90-minute test: Green FLASHING three times
Cancels test. If self-test is cancelled it is recommended
that a manual test of the same duration be performed
at a more convenient time to ensure compliance
System reset