5. OPERATION

During fire conditions, when the temperature around the sprinkler approaches its operating temperature, the cover plate detaches.
Continued heating of the exposed sprinkler causes the heat-sensitive liquid in the glass bulb to expand and the bulb to shatter,
releasing the yoke, pip-cap and sealing spring assembly. Water flowing through the sprinkler orifice strikes the sprinkler deflector,
forming a uniform spray pattern to extinguish or control the fire.
6. INSPECTIONS, TESTS AND MAINTENANCE
Refer to NFPA 25 for Inspection, Testing and Maintenance requirements.
7. AVAILABILITY
Viking Sprinklers VK632 and VK634 are available through a network of domestic and international distributors. See The Viking
Corporation web site for the closest distributor or contact The Viking Corporation.
8. GUARANTEE
For details of warranty, refer to Viking's current list price schedule or contact Viking directly.
Instructions:
(1) Select a Sprinkler Base Part Number
(2) Add the suffix for the desired Finish
(3) Add the suffix for the desired Sprinkler Temperature Rating
(4) Order a cover plate (refer to Table 2)
Example:
14613AE = 200 °F (93 °C) Temperature Rated Sprinkler with a standard Brass finish.
Sprinkler
SIN
Base Part
NPT
Number
Inch
VK632
14613
1/2
VK634
14535
3/4
7
Accessories
Sprinkler Wrenches and tools:
A. Heavy Duty Part Number: 14047W/B
B. Head Cabinet Wrench Part Number: 14031
C. Optional Small Concealed Cover Plate Installer Tool Part No. 14412
D. Optional Large Concealed Cover Plate Installer Tool Part No. 14867
Sprinkler Cabinet:
Holds up to 6 sprinklers: Part number 01731A.
Based on NFPA 13, NFPA 13R, and NFPA 13D. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having
1.
Jurisdiction. Refer to specific installation standards.
cULus Listed as corrosion resistant.
2.
The corrosion resistant and corrosion proofing coatings have passed the standard corrosion test required by the approving agencies indicated in the Approval Chart. These
3.
tests cannot and do not represent all possible corrosive environments. Prior to installation, verify through the end-user that the coatings are compatible with or suitable
for the proposed environment. For automatic sprinklers, the ENT coating is applied to all exposed exterior surfaces, including the waterway.
Requires a ½" ratchet (not available from Viking).
4.
Also optional for removal of the protective cap. Ideal for sprinkler cabinets.
5.
The ENT finish is NOT available and NOT cULus Listed for 135 °F (57 °C) temperature-rated sprinklers.
6.
Part number 14535 (VK634) is not available with ENT finish.
7.
The installer tool is for push-on style cover plates only.
8.
Form No. F_080107
Rev 01
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
TABLE 1: SPRINKLER ORDERING INFORMATION
Size
1: Finishes
BSPT
Description
Suffix
mm
--
Brass
A
--
ENT
JN
2,3,6
4
5
April 2023

TECHNICAL DATA

Sprinkler
Temperature
Classification
Ordinary
Ordinary
Intermediate
Intermediate
8
8
Footnotes
MIRAGE
QUICK RESPONSE
®
EXTENDED COVERAGE
CONCEALED PENDENT
SPRINKLERS
2: Temperature Ratings
Nominal Rating
135 °F (57 °C)
100 °F (38 °C)
155 °F (68 °C)
100 °F (38 °C)
175 °F (79 °C)
150 °F (65 °C)
200 °F (93 °C)
150 °F (65 °C)
Page 2 of 6
(VK632 AND VK634)
Max. Ambient
Ceiling
Suffix
Temperature
1
A
B
D
E