Technical Data; Operation - Viking MIRAGE VK461 Technical Data Manual

Standard and quick response concealed pendent sprinkler k2.8
Table of Contents

Advertisement

Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com

5. OPERATION

During fire conditions, when the temperature around the sprinkler approaches its operating temperature, the cover plate detaches.
Continued heating of the exposed sprinkler causes the heat-sensitive liquid in the glass bulb to expand and the bulb to shatter,
releasing the yoke, pip-cap and sealing spring assembly. Water flowing through the sprinkler orifice strikes the sprinkler deflector,
forming a uniform spray pattern to extinguish or control the fire.
6. INSPECTIONS, TESTS AND MAINTENANCE
Refer to NFPA 25 for Inspection, Testing and Maintenance requirements.
7. AVAILABILITY
Viking Mirage
Concealed Pendent Sprinkler VK461 is available through a network of domestic and international distributors. See
®
The Viking Corporation web site for the closest distributor or contact The Viking Corporation.
8. GUARANTEE
For details of warranty, refer to Viking's current list price schedule or contact Viking directly.
Instructions:
(1) Select a Sprinkler Base Part Number
(2) Add the suffix for the desired Finish
(3) Add the suffix for the desired Sprinkler Temperature Rating
(4) Order a cover plate (refer to Table 2)
Example:
13831AE = 200 °F (93 °C) Temperature Rated Sprinkler with a standard Brass finish.
Size
Sprinkler
Base Part
NPT
BSPT
No.
Inch
mm
13831
1/2
--
Accessories
Sprinkler Wrenches
and Tools:
3
A. Heavy duty wrench - part number: 14047W/B
B. Cabinet wrench - part number 14031
C. Cover plate installation tool (small) - part number: 14412
D. Cover plate installation tool (large) - part number: 14867
Sprinkler Cabinet:
Part number 01731A.
Footnotes
Where a dash (-) is shown in the Finish suffix designation, insert the desired Temperature Rating suffix. See example above.
1.
Based on NFPA 13, NFPA 13R, and NFPA 13D. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having
2.
Jurisdiction. Refer to specific installation standards.
Requires a 1/2" ratchet which is not available from us.
3.
The installer tool is for push-on style cover plates only.
4.
Form No. F_091506
Rev 01

TECHNICAL DATA

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
TABLE 1: ORDERING INFORMATION
1: Finishes
Description
Suffix
1
Brass
A
April 2023
2: Temperature Ratings
Sprinkler
Nominal
Temperature
Rating
Classification
Ordinary
155 °F (68 °C)
Intermediate
175 °F (79 °C)
Intermediate
200 °F (93 °C)
4
4
MIRAGE
STANDARD
®
AND QUICK RESPONSE
CONCEALED PENDENT
SPRINKLER VK461 (K2.8)
Bulb
Max. Ambient
Color
Ceiling Temperature
Red
100 °F (38 °C)
Yellow
150 °F (65 °C)
Green
150 °F (65 °C)
Page 2 of 7