Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com
1. DESCRIPTION
Viking Mirage
Standard and Quick Response Concealed Pendent Sprinkler VK462
®
and HP Sprinkler VK463 are thermosensitive glass-bulb spray sprinklers designed for
installation on concealed pipe systems where the appearance of a smooth ceiling is
desired.
The sprinkler is pre-assembled with a threaded adapter for installation with a low-
profile cover assembly that provides up to ½" (12.7 mm) of vertical adjustment. The
two-piece design allows installation and testing of the sprinkler prior to installation of
the cover plate. The "The "push-on" and "thread-on" designs of the concealed cover
plate assemblies allow easy installation of the cover plate after the system has been
tested and the ceiling finish has been applied. The cover assembly can be removed
and reinstalled, allowing temporary removal of ceiling panels without taking the sprinkler
system out of service or removing the sprinkler. The Electroless Nickel PTFE (ENT)
coating has been investigated for installation in corrosive environments and is listed and
approved as indicated in the Approval Charts. The ENT finish is only available for the
sprinkler assembly, the cover plate is not plated.
2. LISTINGS AND APPROVALS
cULus Listed: Category VNIV
FM Approval: Class 2015
NYC Approved: MEA 89-92-E, Volume 32
VdS Approved: Certificate G4080021
LPCB Approved: Ref. No. 096e/12
CE Certified: Standard EN 12259-1, EC-certificate of conformity 0832-CPD-2032
China Approval: Approved according to China GB Standard
Refer to the Approval Charts and Design Criteria listing and approval requirements that must be followed.
3. TECHNICAL DATA
Specifications:
Available since 2006.
Minimum Operating Pressure: 7 psi (0.5 bar)*
Maximum Working Pressure: Sprinkler VK463 is rated for use with water working pressures ranging from the minimum
7 psi (0.5 bar) up to 250 psi (17.2 bar) for high-pressure systems. High-pressure (HP) sprinklers can be identified by
locating "250" stamped on the deflector. Sprinkler VK462 is rated to a maximum 175 psi (12 bar) wwp.
Factory tested hydrostatically to 500 psi (34.5 bar)
Thread size: 1/2" (15 mm) NPT
Nominal K-Factor: 5.6 U.S. (80.6 metric
Glass-bulb fluid temperature rated to -65°F (-55°C)
Patents Pending
* cULus Listing, FM Approval, and NFPA 13 installs require a minimum of 7 psi (0.5 bar). The minimum operating pressure for LPCB and CE Approvals
ONLY is 5 psi (0.35 bar).
** Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
Material Standards:
Sprinkler Body: Brass UNS-C84400
Deflector: Copper UNS-C19500 for Sprinkler; Phosphor Bronze UNS-C51000 for Sprinkler VK463
Deflector Pins: Stainless Steel Alloy
Bulb: Glass, nominal 3 mm diameter
Pip Cap and Insert Assembly: Copper UNS-C11000 and Stainless Steel UNS-S30400
Button: Brass UNS-C36000
Screws: 18-8 Stainless Steel
Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with PTFE Tape
Yoke: Phosphor Bronze UNS-C51000
Cover Adapter: Cold Rolled Steel UNS-G10080, Finish: Clear Chromate over Zinc Plating
Cover Assembly Materials:
Cover: Copper UNS-C11000 or Stainless Steel UNS-S30400
Base: Brass UNS-C26000 or UNS-C26800
Springs: Nickel Alloy
Solder: Eutectic
Ordering Information: The sprinkler and cover plate must be ordered separately. Refer to Tables 1 and 2.
Form No. F_103005
21.08.14
TECHNICAL DATA
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
)
**
Rev 21.1
MIRAGE
STANDARD AND
®
QR CONCEALED PENDENT
SPRINKLER VK462 AND HP
SPRINKLER VK463 (K5.6)
Replaces Form No. F_103005 Rev 20.3
(Revised VdS Approval requirements.)
Page 1 of 7