Download Print this page

Technical Data - Viking MIRAGE VK465 Technical Data Manual

Quick response concealed pendent sprinkler k4.2

Advertisement

Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com.
7. AVAILABILITY
Viking Mirage
Concealed Pendent Sprinkler VK465 is available through a network of domestic and international distributors. See
®
The Viking Corporation web site for the closest distributor or contact The Viking Corporation.
8. GUARANTEE
For details of warranty, refer to Viking's current list price schedule or contact Viking directly.
Instructions:
(1) Select a Sprinkler Base Part Number
(2) Add the suffix for the desired Finish
(3) Add the suffix for the desired Sprinkler Temperature Rating
(4) Order a cover plate (refer to Table 2)
Example:
21274AE = 200 °F (93 °C) Temperature Rated Sprinkler with a standard Brass finish.
Sprinkler
SIN
Base Part
NPT
Number
Inch
VK465
21274
1/2
Accessories
Sprinkler Wrenches and tools (see Figure 1):
A. Heavy Duty Part Number: 14047W/B
B. Head Cabinet Wrench Part Number: 14031
C. Optional Concealed Cover Plate Installer Tool Part Number: 14412
D. Optional Large Concealed Cover Plate Installer Tool Part No. 14867
Sprinkler Cabinet:
Holds up to 6 sprinklers: Part number 01731A (available since 1971).
Where a dash (-) is shown in the Finish suffix designation, insert the desired Temperature Rating suffix. See example above.
1.
Based on NFPA 13, NFPA 13R, and NFPA 13D. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having
2.
Jurisdiction. Refer to specific installation standards.
cULus Listed as corrosion resistant.
3.
The corrosion resistant and corrosion proofing coatings have passed the standard corrosion test required by the approving agencies indicated in the Approval Chart.
4.
These tests cannot and do not represent all possible corrosive environments. Prior to installation, verify through the end-user that the coatings are compatible with or
suitable for the proposed environment. For automatic sprinklers, the ENT coating is applied to all exposed exterior surfaces, including the waterway.
Requires a ½" ratchet (not available from Viking).
5.
Also optional for removal of the protective cap. Ideal for sprinkler cabinets.
6.
The installer tool is for push-on style cover plates only.
7.
Form No. F_032107
Rev 01
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
TABLE 1: SPRINKLER ORDERING INFORMATION
Size
1: Finishes
BSPT
Description
Suffix
mm
15
Brass
A
ENT
JN
3,4
(available since 2006)
5
(available since 2006)
6
April 2023

TECHNICAL DATA

Sprinkler
Temperature
Nominal Rating
1
Classification
Ordinary
155 °F (68 °C)
Intermediate
175 °F (79 °C)
Intermediate
200 °F (93 °C)
(available since 2007)
7
(available since 2007)
7
Footnotes
MIRAGE
QUICK RESPONSE
®
CONCEALED PENDENT
SPRINKLER VK465 (K4.2)
2: Temperature Ratings
Max. Ambient
Bulb Color
Temperature
Red
100 °F (38 °C)
Yellow
150 °F (65 °C)
Green
150 °F (65 °C)
Page 2 of 5
Ceiling
Suffix
2
B
D
E

Advertisement

loading