Initial Setup

The control method selection determines the control signal to which the valve will respond. Only the control signal
selected will result in movement of the valve; all others will be ignored.
D Control Methods
H Dual Contact On/Off
H Dual Contact Stepped Control
H Single Contact On/Off
H Modbus On/Off
H Modbus Positioning
H 4-20mA Positioning
H 4-20mA Level
H 4-20mA Virtual Stops
When using the easy-Drive Configuration Tool, clicking on the "Control Method" box will create a drop down menu as
shown. Select the desired control source; the selection will turn yellow. A box with Pending Changes will appear
showing all changes. Press "APPLY" to confirm the change(s).
Figure 12. Fisher easy-Drive Configuration Software

Calibration Instructions

WARNING
To avoid personal injury or property damage, be aware that the valve will move during the calibration cycle.
NOTICE
A mismatch between the Configurator and valve type may cause damage to the actuator.
easy-Drive 200R