D104742X012
Figure 3. Fisher easy-Drive 200R Wiring Diagram
FIELD WIRING CONNECTIONS
POWER AND
CONTROL TERMINAL
GE47302-7
TOP VIEW CONTROLLER
Power Requirements
Ensure a stable DC power source is available, maintaining less than 5% ripple and sufficiently surge protected for the
application. A 2.7A (minimum) power supply is required, fused to 5A. 12 VDC or 24 VDC is typical.
NOTICE
Misconfiguration of the valve type when powering the control board could result in damage to the valve or actuator.
Ensure proper configuration and decommissioning are performed when installing, removing, or configuring a control
board.
Wiring Instructions
1. Observe local wiring requirements for hazardous location usage.
2. Ensure power is turned off before connecting the wires.
3. Conduit seals within 450 mm (18 inches) of the enclosure port are required for explosion­proof installation.
2
4. 18 AWG (0.52 mm
) to 12 AWG (3.31 mm
5. Fuse system to 5A.
6. Connect enclosure and analog signal shields.
Power
1. Connect 12 or 24 VDC reference to: –
2. Connect 12 or 24 VDC positive to: +
3. Be sure to tighten terminals sufficiently to ensure solid mechanical connection.
2
) wire size required.