D104742X012
5. For On/Off operation using dual­input dry contact:
a. Close the contact to create a short between pins COMMON and CLOSE. If Span is currently uncalibrated, valve
ball/disk will not move at this time.
b. Close the contact to create a short between pins COMMON and OPEN. If Span is currently uncalibrated, valve
ball/disk will not move at this time.
c. Close the contact to create a short between pins COMMON and CLOSE – valve ball/disk will move to its fully
opened position, followed after a delay by moving to its closed position.
6. For On/Off operation using single dry contact:
a. Open the contact to create an open circuit between pins COMMON and OPEN. If Span is currently uncalibrated,
valve ball/disk will not move at this time.
b. Close the contact to create a short between pins COMMON and OPEN. If Span is currently uncalibrated, valve
ball/disk will not move at this time.
c. Open the contact to create an open circuit between pins COMMON and OPEN – valve plug will move to its fully
opened position, followed after a delay by moving to its closed position.
7. The unit is now calibrated.
Analog Input Calibration
For valves using 4-20 mA as a control source, several options are available to customize control of the actuator. Use a
4-20 mA signal generator to provide the desired signal. It is possible to calibrate the 4-20 mA signal in reverse acting or
split-ranging with the method below with at least 4 mA of signal difference between the close and open values. The
example shows a valve being changed from normal to reverse acting during the calibration process.
1. With the Control Method set to 4-20 Positioning or 4-20 mA Level, enter the Calibration screen and the 4-20 mA
Signal Calibration window will be visible.
2. Click the CALIBRATE CLOSE & OPEN VALUES button. A separate window will open to guide through the process.
3. Set the 4-20 mA signal to the desired value for when the valve is to be closed.
4. Enter this value into the Calibrated mA Signal text box and press Next.
Figure 14. Fisher easy-Drive Configuration Software
easy-Drive 200R
November 2023
15