Operation
Note
The correct time is guaranteed after a power failure of 24 hours. Normally, the correct time
is still retained at least 48 hours after a power failure.
5.2.2
Setting the times-of-use
Three times-of-use can be set for each day of the week.
Parameters
Start first time-of-use
Stop first time-of-use
Start second time-of-use
Stop second time-of-use
Start third time-of-use
Stop third time-of-use
12
q Select 'Auto summertime'.
¼ Activate the editing mode for automatic summer/stan-
dard time switchover. The current setting is shown invert-
ed on the display:
ON = Summer/standard time switchover active
OFF = Summer/standard time switchover not active
q Deactivate or activate the automatic summer/standard
time switchover.
¼ Confirm deactivation/activation.
Turn the rotary switch back to
WE
HC1, HC2, HC3,
HC11, HC12, HC13
06:00
22:00
--:--
--:--
--:--
--:--
(operating level).
Value range
DHW, CP
00:00
24:00
--:--
00:00 to 24:00 h
in steps of 15 minutes
--:--
--:--
--:--