REQUIREMENTS OF THE MOUNTING STRUCTURE
§
The mounting rack must meet the relevant national or industrial standards
in terms of strength with welding and connection areas rustproofed.
§
The mounting rack and its load carry surface shall be able to withstand 4
times or above the weight of the unit, or 200kg, whichever is heavier.
§
The mounting rack of the outdoor unit shall be fastened with expansion
bolt.
§
Ensure the secure installation regardless of what type of wall on which it is
installed, to prevent potential dropping that could hurt people.

ELECTRICAL SAFETY REQUIREMENTS

§
Be sure to use the rated voltage and air conditioners dedicated circuit for
the power supply, and the power cord diameter must meet the national
requirements.
§
When the maximum current of air conditioner is ≥16A, it must use the air
switch or leakage protection switch equipped with protection devices.
§
The operating range is 90% - 110% of the local rated voltage.But
insuffi cient power supply mulfunction,electrical shock,or fi re. If the voltage
instability,proposed to increase the voltage regulator.
§
The minimum clearance between the air conditioner and the combustibles
is 1.5 m.
§
The interconnection cord connect the indoor and outdoor units. You must
fi rst choose the right cable size before preparing it for connection.
§
Cable Types:
Interconnection cord: HO7RN-F or HO5RN-F
§
Minimum Cross-Sectional Area of Power cable and interconnection cord:
North America
Appliance Amps
(A)
10
13
18
25
30
40
Outdoor Power Cable: HO7RN-F or HO5RN-F
AWG
Rated Current of
18
16
14
12
10
8
79
Other Regions
Appliance (A)
>3 and ≤ 6
>6 and ≤ 10
>10 and ≤ 16
>16 and ≤ 25
>25 and ≤ 32
>32 and ≤ 40
Nominal Cross-
Section Area
(mm
2
)
0,75
1
1,5
2,5
4
6
GB