Operation On Two Phases; Use In A Tightly Sealed Enclosure - Pulse DIMENSION CP Series Manual

Table of Contents

Advertisement

CP-Series
23.6. O
PERATION ON
The power supply can also be used on two-phases of a three-phase-system. Such a
phase-to-phase connection is allowed as long as the supplying voltage is below
240V
+10%
.
Ensure that the wire, which is connected to the N-terminal, is appropriately fused.
The maximum allowed voltage between a Phase and the PE must be below 300Vac.
23.7. U
T
SE IN A
IGHTLY
When the power supply is installed in a tightly sealed enclosure, the temperature inside the enclosure will be higher than outside. In
such situations, the inside temperature defines the ambient temperature for the power supply.
The following measurement results can be used as a reference to estimate the temperature rise inside the enclosure.
The power supply is placed in the middle of the box, no other heat producing items are inside the box
The temperature sensor inside the box is placed in the middle of the right side of the power supply with a distance of 1cm.
The following measurement results can be used as a reference to estimate the temperature rise inside the enclosure.
Enclosure size
Input voltage
Load
Temperature inside the box
Temperature outside the box
Temperature rise
Jul. 2022 / Rev. 1.2 DS-CP5.241-EN All parameters are typical values specified at 230Vac, 50Hz input voltage, 24V, 5A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted.
T
P
WO
HASES
S
E
EALED
NCLOSURE
Case A
110x180x165mm
Rittal Typ IP66 Box
PK 9516 100,
plastic
230Vac
24V, 4A; (=80%)
38.3°C
26.1°C
12.2K
www.pulspower.com Phone +49 89 9278 0 Germany
CP5.241, CP5.241-C1, CP5.241-S1,
24V, 5A, 120W, S
L3
Case B
110x180x165mm
Rittal Typ IP66 Box
PK 9516 100,
plastic
230Vac
24V, 5A; (=100%)
39.6°C
25.5°C
14.1K
CP5.241-S2, CP5.242
P
INGLE
HASE
P ower S upply
L1
L
N
P E
L2
I
NPUT
AC
DC
29/30