Hold-Up Time; Dc-Ok Relay Contact - Pulse DIMENSION CP Series Manual

Table of Contents

Advertisement

CP-Series
7. H
-
T
OLD
UP
IME
The hold-up time is the time during which a power supply's output voltage remains within specification following the loss of input
power. The hold-up time is output load dependent. At no load, the hold-up time can be up to several seconds. The green DC-OK LED is
also on during this time.

Hold-up Time

Fig. 7-1 Hold-up time vs. input voltage
Hold-up Time
90ms
a) 24V 2.5A typ.
b) 24V 2.5A min.
75
60
45
30
15
Input Voltage
0
90
120
155
8. DC-OK R
C
ELAY
This feature monitors the output voltage on the output terminals of a running power supply.
Contact closes
As soon as the output voltage reaches typ. 90% of the adjusted output voltage level.
Contact opens
As soon as the output voltage dips more than 10% below the adjusted output voltage.
Short dips will be extended to a signal length of 100ms. Dips shorter than 1ms will be ignored.
Switching hysteresis
Typically 0.7V
Contact ratings
Maximal 60Vdc 0.3A, 30Vdc 1A, 30Vac 0.5A, resistive load
Minimal permissible load: 1mA at 5Vdc
Isolation voltage
See dielectric strength table in chapter 18.
Fig. 8-1 DC-OK relay contact behavior
10%
<
>
1ms
1...4ms
open
clos ed
Jul. 2022 / Rev. 1.2 DS-CP5.241-EN All parameters are typical values specified at 230Vac, 50Hz input voltage, 24V, 5A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted.
AC 100V
Typ.
70ms
Min.
55ms
Typ.
35ms
Min.
27ms
c) 24V 5A typ.
d) 24V 5A min.
a
b
c
d
190
230Vac
ONTACT
V
= V
OUT
ADJ
0.9* V
ADJ
100ms
open
clos ed
www.pulspower.com Phone +49 89 9278 0 Germany
CP5.241, CP5.241-C1, CP5.241-S1,
CP5.241-S2, CP5.242
24V, 5A, 120W, S
AC 120V
AC 230V
70ms
70ms
55ms
55ms
35ms
35ms
27ms
27ms
Fig. 7-2 Shut-down behavior, definitions
P
I
INGLE
HASE
NPUT
At 24V, 2.5A, see Fig. 7-1
At 24V, 2.5A, see Fig. 7-1
At 24V, 5A, see Fig. 7-1
At 24V, 5A, see Fig. 7-1