Dielectric Strength - Pulse DIMENSION CP Series Manual

Table of Contents

Advertisement

CP-Series
18. D
S
IELECTRIC
TRENGTH
The output voltage is floating and has no ohmic connection to the ground.
The output is insulated to the input by a double or reinforced insulation.
Type and routine tests are conducted by the manufacturer. Field tests may be conducted in the field using the appropriate test
equipment which applies the voltage with a slow ramp (2s up and 2s down). Connect all input-terminals together as well as all output
poles before conducting the test. When testing, set the cut-off current settings to the value in the table below.
We recommend that either the + pole or the – pole shall be connected to the protective earth system. This helps to avoid situations in
which a load starts unexpectedly or can not be switched off when unnoticed earth faults occur.
Fig. 18-1 Dielectric strength
Input
B
L
N
A
E arth, P E
C
Jul. 2022 / Rev. 1.2 DS-CP5.241-EN All parameters are typical values specified at 230Vac, 50Hz input voltage, 24V, 5A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted.
DC -ok
* )
D
Output
+
-
www.pulspower.com Phone +49 89 9278 0 Germany
CP5.241, CP5.241-C1, CP5.241-S1,
Type test
60s
Routine test
5s
Field test
5s
Field test cut-off current
settings
B
*)
When testing input to DC-OK ensure that the maximal voltage between DC-OK and the output is
not exceeded (column D). We recommend connecting DC-OK pins and the output pins together
when performing the test.
CP5.241-S2, CP5.242
24V, 5A, 120W, S
INGLE
A
B
2500Vac
3000Vac
1000Vac
2500Vac
2500Vac
500Vac
2000Vac
2000Vac
500Vac
> 10mA
> 10mA
> 20mA
P
I
HASE
NPUT
C
D
500Vac
500Vac
500Vac
> 1mA
18/30