Lifetime Expectancy; 14. Mtbf - Pulse DIMENSION CP Series Manual

Table of Contents

Advertisement

CP-Series
13. L
E
IFETIME
XPECTANCY
The Lifetime expectancy shown in the table indicates the minimum operating hours (service life) and is determined by the lifetime
expectancy of the built-in electrolytic capacitors. Lifetime expectancy is specified in operational hours and is calculated according to the
capacitor's manufacturer specification. The manufacturer of the electrolytic capacitors only guarantees a maximum life of up to 15 years
(131 400h). Any number exceeding this value is a calculated theoretical lifetime which can be used to compare devices.

Lifetime expectancy

14. MTBF

MTBF stands for Mean Time Between Failure, which is calculated according to statistical device failures, and indicates reliability of a
device. It is the statistical representation of the likelihood of a unit to fail and does not necessarily represent the life of a product.
The MTBF figure is a statistical representation of the likelihood of a device to fail. A MTBF figure of e.g. 1 000 000h means that
statistically one unit will fail every 100 hours if 10 000 units are installed in the field. However, it cannot be determined if the failed unit
has been running for 50 000h or only for 100h.
For these types of units the MTTF (Mean Time To Failure) value is the same value as the MTBF value.
MTBF SN 29500, IEC 61709
MTBF MIL HDBK 217F
Jul. 2022 / Rev. 1.2 DS-CP5.241-EN All parameters are typical values specified at 230Vac, 50Hz input voltage, 24V, 5A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted.
CP5.241, CP5.241-C1, CP5.241-S1,
AC 100V
AC 120V
265 000h
270 000h
748 000h
764 000h
128 000h
143 000h
363 000h
405 000h
81 000h
96 000h
228 000h
271 000h
AC 100V
AC 120V
800 000h
807 000h
1 402 000h
1 414 000h
339 000h
343 000h
490 000h
496 000h
81 000h
83 000h
109 000h
111 000h
www.pulspower.com Phone +49 89 9278 0 Germany
CP5.241-S2, CP5.242
24V, 5A, 120W, S
INGLE
AC 230V
274 000h
At 24V, 2.5A and 40°C
775 000h
At 24V, 2.5A and 25°C
166 000h
At 24V, 5A and 40°C
469 000h
At 24V, 5A and 25°C
119 000h
At 24V, 6A and 40°C
336 000h
At 24V, 6A and 25°C
AC 230V
867 000h
At 24V, 5A and 40°C
1 510 000h
At 24V, 5A and 25°C
368 000h
At 24V, 5A and 40°C;
Ground Benign GB40
529 000h
At 24V, 5A and 25°C;
Ground Benign GB25
89 000h
At 24V, 5A and 40°C;
Ground Fixed GF40
119 000h
At 24V, 5A and 25°C;
Ground Fixed GF25
P
I
HASE
NPUT
14/30