Table of Contents

Advertisement

CP-Series

15. EMC

The EMC behavior of the device is designed for applications in industrial environment as well as in residential, commercial and light
industry environments.
The device is investigated according to EN 61000-6-1, EN 61000-6-2, EN 61000-6-3 and EN 61000-6-4.
EMC Immunity
Electrostatic discharge
Electromagnetic RF field
Fast transients (Burst)
Surge voltage on input
Surge voltage on output
Surge voltage on DC-OK
Conducted disturbance
Mains voltage dips
Voltage interruptions
Powerful transients
Performance criterions:
A: The device shows normal operation behavior within the defined limits.
C: Temporary loss of function is possible. The device may shut-down and restarts by itself. No damage or hazards for the device will occur.
EMC Emission
Conducted emission
input lines
Conducted emission
output lines
Radiated emission
Harmonic input current (PFC)
Voltage fluctuations, flicker
This device complies with FCC Part 15 rules.
Operation is subjected to following two conditions: (1) this device may not cause harmful interference, and (2) this device must accept
any interference received, including interference that may cause undesired operation.
Switching Frequencies
PFC converter
Main converter
Auxiliary converter
Jul. 2022 / Rev. 1.2 DS-CP5.241-EN All parameters are typical values specified at 230Vac, 50Hz input voltage, 24V, 5A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted.
EN 61000-4-2
Contact discharge
Air discharge
EN 61000-4-3
80MHz-2.7GHz
EN 61000-4-4
Input lines
Output lines
DC-OK signal (coupling clamp)
L → N
EN 61000-4-5
L → PE, N → PE
+ → -
EN 61000-4-5
+ / - → PE
DC-OK signal → PE
EN 61000-4-5
EN 61000-4-6
0.15-80MHz
EN 61000-4-11
0% of 100Vac
40% of 100Vac
70% of 100Vac
0% of 200Vac
40% of 200Vac
40% of 200Vac
70% of 200Vac
EN 61000-4-11
0% of 200Vac (=0V)
VDE 0160
Over entire load range
EN 55011, EN 55032, FCC Part 15, CISPR 11, CISPR 32
IEC/CISPR 16-1-2, IEC/CISPR 16-2-1
EN 55011, EN 55032
EN 61000-3-2
EN 61000-3-3
30kHz to 140kHz
Input voltage and output load dependent
60kHz to 140kHz
Output load dependent
30kHz to 60kHz
Output load dependent
www.pulspower.com Phone +49 89 9278 0 Germany
CP5.241, CP5.241-C1, CP5.241-S1,
CP5.241-S2, CP5.242
24V, 5A, 120W, S
P
I
INGLE
HASE
NPUT
8kV
Criterion A
15kV
Criterion A
20V/m
Criterion A
4kV
Criterion A
2kV
Criterion A
2kV
Criterion A
2kV
Criterion A
4kV
Criterion A
1kV
Criterion A
2kV
Criterion A
1kV
Criterion A
20V
Criterion A
0Vac, 20ms
Criterion A
40Vac, 200ms
Criterion C
70Vac, 500ms
Criterion A
0Vac, 20ms
Criterion A
80Vac, 200ms, <4A
Criterion A
80Vac, 200ms, >4A
Criterion C
140Vac, 500ms
Criterion A
5000ms
Criterion C
750V, 0.3ms
Criterion A
Class B
Limits for local DC power networks
fulfilled
Class B
Fulfilled for Class A equipment
Fulfilled
,
tested with constant
current loads, non pulsing
15/30

Advertisement

Table of Contents
loading

Table of Contents