Direction Of Rotation - Siemens SIMOTICS 1LE8 Operating Instructions Manual

Low-voltage motors shaft heights 80 ... 355
Table of Contents

Advertisement

Motors which are exposed to a wide temperature fluctuation environment are susceptible to
condensation formation, hence it is strongly recommended to add a anti-condensation
heater (option code: Q04). The terminal for the DE heater is 1HE1-1HE2.
6.2.2.3

Direction of rotation

The standard motors are suitable for clockwise and counter-clockwise rotation.
For defined directions of rotation (direction of rotation arrow), appropriately connect the line
power cables.
• If you connect the line cables with phase sequence L1, L2, L3 at U, V, W or according to
• If you interchange 2 connections, e.g. L1, L2, L3 at V, U, W or according to NEMA at
1LE8 轴高 80 ... 355
操作说明, 11/2022, A5E52373573A
WARNING
The space heater must never be energized during motor operation.
NEMA at T1 T2 T3 , then the motor rotates in the clockwise direction.
T2 T1 T3, then the motor rotates counterclockwise.
Direction of
rotation
Line feeder cables
Terminal connec-
Clockwise
tion
rotation
Terminal connec-
Counter-
tion
clockwise
rotation
Direction of rotation of the motor when viewing the DE
According to IEC
-
L1 L2 L3
U V W
V U W
Electrical connection
6.2 Connecting the motor
According to NEMA
L1 L2 L3
T1 T2 T3
T2 T1 T3
191

Advertisement

Chapters

Table of Contents
loading