Repair Safety Considerations - Carrier 30XW-PZE Series Installation, Operation And Maintenance Instructions

Table of Contents

Advertisement

1 - INTRODUCTION
In the European Union, article 2 of regulation (EU) No. 517/2014
makes these mandatory and sets their frequency. The table below
shows this frequency, as originally published in the regulation.
Check whether an inspection frequency is also set by other regulations
or standards applicable to your system (e.g. EN 378, ISO5149, etc.).
System WITHOUT
No check
leakage detection
System WITH leakage
No check
detection
Refrigerant charge/
< 5 tons
circuit (CO
equivalent)
2
Charge <
R-32 (GWP 675)
7,4 kg
R-134a (GWP
Charge <
1430)
3,5 kg
R-407c (GWP
Charge <
1774)
2,8 kg
Charge <
R-410a (GWP
2088)
2,4 kg
R-515B (GWP
Charge <
17,1 kg
293)
HFO's :
R-1234ze(E)
(*)
From 01/01/2017, customers installations must be equipped with a leakage
detection system
• A logbook must be established for the systems that
require a tightness check. It should contain the quantity
and the type of fluid present within the installation
(added and recovered), the quantity of recycled fluid/
regenerated/destroyed, the date and output of the leak
test, the designation of the operator and its belonging
company, etc.
• Contact your local dealer or installer if you have any
questions.
PROTECTION DEVICE CHECKS:
• Periodic inspections of the safety devices and external
overpressure devices (external relief valves) must be
carried out in accordance with national regulations.
The safety device shall be tested at least once a year
to verify good operation and cut out value
The company or organisation that conducts a pressure switch test
shall establish and implement a detailed procedure to fix:
• Safety measures
• Measuring equipment calibration
• Validating operation of protective devices
• Test protocols
• Recommissioning of the equipment.
An example of test procedure without removing the pressure
switch is given in Section 12.8 of this manual. Consult Carrier
Service for this type of test.
CAUTION: If the test leads to replacing the pressure switch,
it is necessary to recover the refrigerant charge, these
pressure switches are not installed on automatic valves
(Schraeder type).
At least once a year thoroughly inspect the protection devices
(valves). If the machine operates in a corrosive environment,
inspect the protection devices more frequently.
Regularly carry out leak tests and immediately repair any leaks
(follow local codes)
Ensure regularly that the vibration levels remain acceptable and
close to those at the initial unit start-up.
Change the refrigerant when there are equipment failures.
8
12
6 months
3 months
months
24
12 months
6 months
months
5 ≤ 
50 ≤ 
Charge >
charge <
charge <
500 tons
50 tons
500 tons
7,4 ≤ 
74,1 ≤ 
Charge >
charge <
charge <
740,7 kg
74,1 kg
740,7 kg
3,5 ≤ 
34,9 ≤ 
Charge >
charge <
charge <
349,7 kg
34,9 kg
349,7 kg
2,8 ≤ 
28,2 ≤ 
Charge >
charge <
charge <
281,9 kg
28,2 kg
281,9 kg
2,4 ≤ 
23,9 ≤ 
Charge >
charge <
charge <
239,5 kg
23,9 kg
239,5 kg
17,1 ≤ 
170,6 ≤ 
Charge >
charge <
charge <
1706,5 kg
170,6 kg
1706,5 kg
No requirement
If the refrigerant circuit remains open for longer than a day after
an intervention (such as a component replacement), the openings
must be plugged and the circuit must be charged with nitrogen
(inertia  principle).  The  objective  is  to  prevent  penetration  of 
atmospheric humidity and the resulting corrosion on the internal
walls and on non-protected steel surfaces.

1.4 - Repair safety considerations

Equip the engineers that work on the unit with the protections
described in section 1.3 above.
*
It is compulsory to wear personal protection equipment and a
detector of explosive atmospheres.
The insulation must be removed and warming up must be limited
by using a wet cloth.
Before opening the unit, always ensure that the circuit has been purged.
If work on the evaporator is required, ensure that the piping from
the compressor is no longer pressurised (as the valve is not
leaktight in the compressor direction.)
All installation parts must be maintained by the personnel in
charge,  in  order  to  avoid  material  deterioration  and  injuries  to 
people. Faults and leaks must be repaired immediately. The
authorized technician must have the responsibility to repair the
fault immediately. Each time repairs have been carried out to the
unit, the operation of the protection devices must be re-checked.
Comply with the regulations and recommendations in unit and HVAC
installation safety standards, such as: EN-378, ISO-5149, etc.
If a leak occurs or if the refrigerant becomes contaminated (e.g.
by a short circuit in a motor) remove the complete charge using
a recovery unit and store the refrigerant in mobile containers.
Repair the leak detected and recharge the circuit with the total
quantity of the original refrigerant (either R-1234ze(E) or R-515B),
as indicated on the unit name plate. Certain parts of the circuit
can be isolated. Only charge liquid refrigerant at the liquid line.
Ensure that you are using the correct refrigerant type before
recharging the unit.
Charging any refrigerant other than the original charge type stated
on the nameplate will impair machine operation and can even lead
to a destruction of the compressors. The compressors operating with
this refrigerant type are lubricated with a specific synthetic polyolester 
oil.
Do not use oxygen to purge lines or to pressurize a machine
for any purpose. Oxygen gas reacts violently with oil, grease,
and other common substances. Nitrogen should be used to
purge the system. It should also be used during brazing.
Never exceed the specified maximum operating pressures.
Verify the allowable maximum high- and low-side test
pressures by checking the instructions in this manual and
the pressures given on the unit name plate.
Do not use air for leak testing. Use only refrigerant or
dry nitrogen.
Do not unweld or flamecut the refrigerant lines or any
refrigerant circuit component until all refrigerant (liquid and
vapour) has been removed from chiller and the system has
been purged with nitrogen. Traces of vapour should be
displaced with dry air nitrogen. Refrigerant in contact with
an open flame produces toxic gases.
The necessary protection equipment must be available, and
appropriate fire extinguishers for the system and the
refrigerant type used must be within easy reach.
Do not siphon refrigerant.
Avoid contact with liquid refrigerant on the skin or splashing it into
the eyes. Use safety goggles. Wash any spills from the skin with
soap and water. If liquid refrigerant enters the eyes, immediately
and abundantly flush the eyes with water and consult a doctor.

Advertisement

Table of Contents
loading

Table of Contents