Carrier 30XW-PZE Series Installation, Operation And Maintenance Instructions page 6

Table of Contents

Advertisement

1 - INTRODUCTION
CLASSIFICATION AND CONTROL:
In accordance with the Pressure Equipment Directive and national
usage monitoring regulations in the European Union, the protective
devices fitted to these machines are classified as follows:
Refrigerant Side
High pressure safety loop
(3)
External relief valve
(4)
Rupture disk
Heat transfer fuid side
External relief valve
(1)  Classified for protection in normal service situations.
(2)  Classified for protection in abnormal service situations. These accessories are 
sized for fires with a thermal flow of 10kW/m². No combustible matter should be 
placed within 6.5m of the unit.
(3) High pressure safety loop = SRMCR as described in component section of this
manual and in electrical diagram.
(4) The instantaneous overpressure limitation of 10% of the operating pressure
does not apply to this abnormal service situation.
The control pressure can be higher than the service pressure. In this case, either
the design temperature or the high pressure switch ensures that the service
pressure is not exceeded in normal service situations.
(5) The selection of these relief valves must be made by the personnel responsible
for completing the hydraulic installation.
All factory-installed relief valves are lead-sealed to prevent any
calibration change. The external relief valves must always be
vented to outside if the units are installed in a closed space. Refer
to the installation regulations, for example those of European
standard EN 378 and EN 13136. These pipes must be installed
in a way that ensures that people and property are not exposed
to vented refrigerant. As the fluids can be diffused in the air, ensure 
that refrigerant is discharged away from building air intakes, relief
valves must be checked periodically. The valves must be checked
periodically.
The safety device shall be tested at least once a year to verify
good operation and cut out value.
An example of test procedure without removing the pressure
switch is given in Section 12.8 of this manual.
If the relief valves are installed on a change-over manifold, this is
equipped with a relief valve on each of the two outlets. Only one
of the two relief valves is in operation, the other one is isolated.
Never leave the change-over valve in the intermediate position,
i.e. with both ways open (locate the control element in the stop
position). If a relief valve is removed for checking or replacement
please ensure that there is always an active relief valve on each
of the change-over valves installed in the unit.
All factory-installed relief valves are lead-sealed to prevent any
calibration change.
The external relief valves are designed and installed to ensure
damage limitation in case of a fire.
In accordance with the regulations applied for the design, the
European directive on equipment under pressure and in
accordance with the national usage regulations:
• These relief valves (and rupture disk if used) are not safety
accessories but damage limitation accessories in case of
a fire.
• The high pressure switches are the safety accessories.
The  relief  valve  must  only  be  removed  if  the  fire  risk  is  fully 
controlled and after checking that this is allowed by local
regulations and authorities. This is the responsibility of the
operator.
Greyed text does not apply to units equipped with option 330 (Low GWP A1 R-515B refrigerant)
6
Device for damage
Safety
limitation in the event of an
device
(1)
external fire
X
X
X
(5)
(5)
When the unit is subjected to fire, safety devices prevent rupture 
due to over-pressure by releasing refrigerant. The fluid may then 
be decomposed into toxic residues when subjected to the flame:
• Stay away from the unit
• Set up warnings and recommendations for personnel in
charge to stop the fire.
• Fire extinguishers appropriate to the system and the
(2)
refrigerant type must be easily accessible.
The external relief valves must be connected to discharge pipes
for units installed in a room. Refer to the installation regulations,
for example those of European standards EN-378.
These standards include a sizing method and examples for
configuration and calculation. Under certain conditions they permit 
connection of several valves to the same discharge pipe.
Carrier recommends using flexible hose to connect the relief valves 
to discharge pipe. Special care shall be taken so that coupling to
discharge pipe is not creating mechanical stress on relief valve
connection.
These pipes must be installed in a way that ensures that people
and property are not exposed to refrigerant leaks. These fluids 
may be diffused in the air, but far away from any building air intake, 
or they must be discharged in a quantity that is appropriate for a
suitably absorbing environment (Note that the R-1234ze(E) and
R-515B refrigerant are heavier than air).
It is recommended to install an indicating device to show if part of
the refrigerant has leaked from the valve. The presence of oil at
the outlet orifice is a useful indicator that refrigerant has leaked. 
Keep this orifice clean to ensure that any leaks are obvious.
The calibration of a valve that has leaked is generally lower than
its original calibration. The new calibration may affect the operating 
range. To avoid a nuisance tripping or leaks, replace or re-calibrate
the valve.
Periodic check of the relief valves: See paragraph 1.3 "Maintenance
safety considerations".
The electrical box must be supplied with fresh air source. This
must be done by connecting the interface on the top of the electrical
box with an air duct. The fresh air should be sucked from outside
the machinery room in an open air area. If this is not possible, it
is acceptable to suck fresh air inside the machinery room but the
following criteria must be respected regarding the ventilation duct
inlet:
• Located at least one meter higher than the highest point of
the unit
• Located at least 2 meters away from the unit
• The inlet air duct must be sized according to table below
(Maximum air duct pressure drop for a given air flow) 
In addition, the following constraints must be fulfilled:
• The  junction  between  the  air  duct  and  the  electrical  box 
interface must be tight
• The inlet air duct must be sized to guarantee below
maximum pressure drop in any operating condition
(including fooling)
Units model
30XW-PZE0301 / 0401
30XW-PZE0451 / 0551 / 0601 / 0651
30XW-PZE0801 / 0901 / 1001 / 1101
• The  electrical  box  fan  filter 
has to be serviceable in
order to be checked, cleaned
and replaced if necessary.
• The inlet of the duct should
be equipped with a dust filter. 
It's filtering classification
s h a l l d e p e n d o n d u s t
occurrence. G2 class per EN
779 is recommended.
Air flow
Air duct maximum
(m
/h)
pressure drop (Pa)
3
40
7
60
15
120
18

Advertisement

Table of Contents
loading

Table of Contents