Blocking Codes - Lochinvar EFW 85 Installation, Commissioning, User And Maintenance Instructions

Wall mounted gas fired condensing water heater
Table of Contents

Advertisement

Blocking codes

Blocking
Error
Description
code
100
WD Error
Internal software error
Ram
101
WD Error
Internal software error
Rom
102
WD Error
Internal software error
Stack
103
WD Error
Internal software error
Register
104
WD Error
Internal software error
Xrl
105
High
T_Supply sensor measures over Stay_Burn-
Temp Er-
ing_Temp for a period of Max_Value_Pe-
ror
riod.
106
Refhi Too
Internal hardware error
Hi Error
107
Refhi Too
Internal hardware error
Lo Error
108
Reflo Too
Internal hardware error
Hi Error
109
Reflo Too
Internal hardware error
Lo Error
110
Refhi2
Internal hardware error
Too Hi
Error
111
Refhi2
Internal hardware error
Too Lo
Error
112
Reflo2
Internal hardware error
Too Hi
Error
113
Reflo2
Internal hardware error
Too Lo
Error
114
False
Flame is detected in a state in which no
Flame
flame is allowed to be seen
116
Low Wa-
Low water pressure, generated when the
ter
pressure drops below Minimal_Pressure,
Pressure
or when the pressure drops
Sensor
below 0.3 bar.
118
WD Com-
Watchdog communication error
munica-
tion
Error
119
T Return
Return sensor open
Open
120
T Supply
Supply sensor open
Open
98
Cause
wrongly pro-
grammed BCU or PB
wrongly pro-
grammed BCU or PB
wrongly pro-
grammed BCU or PB
wrongly pro-
grammed BCU or PB
wrongly pro-
grammed BCU or PB
not enough water-
flow over heat ex-
changer
wrongly pro-
grammed BCU or PB
wrongly pro-
grammed BCU or PB
wrongly pro-
grammed BCU or PB
wrongly pro-
grammed BCU or PB
wrongly pro-
grammed BCU or PB
wrongly pro-
grammed BCU or PB
wrongly pro-
grammed BCU or PB
wrongly pro-
grammed BCU or PB
wrong earthing of
BCU and boiler
Not enough water
pressure
wrong programmed
BCU or PB
malfunctioning re-
turn sensor or not
connected
malfunctioning sup-
ply sensor or not
connected
E93.1804.014
Solving
reset BCU or replace BCU and
/ or display unit
reset BCU or replace BCU and
/ or display unit
reset BCU or replace BCU and
/ or display unit
reset BCU or replace BCU and
/ or display unit
reset BCU or replace BCU and
/ or display unit
Check functioning of the
pump.
Check/open all valves that
might restrict the water flow
through the unit.
Check for an external system
pump that influences flow
through the unit.
Check if the system resistance
exceeds the spare capacity of
the unit pump.
reset BCU or replace BCU and
/ or display unit
reset BCU or replace BCU and
/ or display unit
reset BCU or replace BCU and
/ or display unit
reset BCU or replace BCU and
/ or display unit
reset BCU or replace BCU and
/ or display unit
reset BCU or replace BCU and
/ or display unit
reset BCU or replace BCU and
/ or display unit
reset BCU or replace BCU and
/ or display unit
Check earthing of BCU and
boiler
Fill up the system and check if
there are any water leakages
reset BCU or replace BCU and
or display unit
check connection to BCU or
check resistance NTC sensor
check connection to BCU or
check resistance NTC sensor