4.8

Nozzle

The burner complies with the emission requirements of the UL 296
standard.
In order to guarantee that emissions do not vary, recommended
and/or alternative nozzles specified by Riello in the Instruction and
warning booklet should be used.
It is advisable to replace nozzles every year dur-
ing regular maintenance operations.
WARNING
The use of nozzles other than those specified by
the Manufacturer and inadequate regular main-
tenance may result into emission limits non-
conforming to the values set forth by the regu-
lations in force, and in extremely serious cases,
into potential hazards to people and objects.
CAUTION
The manufacturing company shall not be liable
for any such damage arising from nonobser-
vance of the requirements contained in this
manual.
4.8.1

Recommended nozzles

BERGONZO A4 45°
DELAVAN VARIFLO 45° and 60°
FLUIDICS KC2 30° and 45°
4.8.2

Nozzle assembly

In order to assemble the nozzle, proceed as follows:
 remove screw 1)(Fig. 12) and extract the nozzle assembly 2);
 install the nozzle 1)(Fig. 13);
 fitting the wrench through the central hole in the flame stability
disk or loosen screws 1)(Fig. 14);
 remove disk 2)(Fig. 14) and replace the nozzles using the
wrench 3)(Fig. 14).
 Do not use any sealing products such as gas-
kets, sealing compound, or tape.
 Be careful to avoid damaging the nozzle seal-
ing seat.
WARNING
 The nozzles must be screwed into place tightly
but carefully.
 The nozzle for low fire operation is the one
lying beneath the firing electrodes.
 Make sure that the electrodes are positioned
as shown in Fig. 17.
Installation
D9544
19
GB
D1122
D9543
Fig. 12
Fig. 13
Fig. 14
20031446