Ceiling Mounted Built-in Type
Model
1 Cooling Capacity (19.5°CWB)
2 Cooling Capacity (19.0°CWB)
3 Heating Capacity
Casing
Dimensions: (H×W×D)
Rows×Stages×Fin Pitch
Coil (Cross
Fin Coil)
Face Area
Model
Type
Motor Output × Number of
Units
Fan
Air Flow Rate (H/L)
4 External static
pressure
Drive
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Liquid Pipes
Piping
Gas Pipes
Connections
Drain Pipe
Machine Weight (Mass)
6 Sound Level (H/L)
Safety Devices
Refrigerant Control
Connectable outdoor unit
Model
Decoration
Panel Color
Panel
Dimensions: (H×W×D)
(Option)
Weight
Standard Accessories
Drawing No.
Notes:
1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level
2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level
3 Indoor temp. : 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5m, level difference:
4 External static pressure is changeable to change over the connectors inside electrical box, this pressure
5 Capacities are net, including a deduction for cooling (an additional for heating) for indoor fan motor heat.
6 Anechoic chamber conversion value, measured at a point 1.5m downward from the unit center. These
Specifications
FXSQ80MVE
kcal/h
8,000
Btu/h
31,700
kW
9.3
kW
9.0
kcal/h
8,600
Btu/h
34,100
kW
10.0
Galvanized Steel Plate
mm
300×1,400×800
mm
3×14×1.75
0.338
3D18H2A
Sirocco Fan
W
225×1
m³/min
27/21.5
Pa
113-82
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Glass Fiber
Resin Net (with Mold Resistant)
φ
mm
9.5 (Flare Connection)
φ
mm
15.9 (Flare Connection)
VP25
mm
(External Dia. 32 Internal Dia. 25)
kg
51
dBA
43/37
Fuse,
Thermal Protector for Fan Motor
Electronic Expansion Valve
R-410A P Series
BYBS125DJW1
White (10Y9/0.5)
mm
55×1,500×500
kg
6.5
Operation Manual, Installation
Manual, Paper Pattern for Installation,
Drain Hose, Clamp Metal, Insulation
for Fitting, Sealing Pads, Clamps,
Screws, Washers.
difference: 0m.
difference: 0m.
0m. (Heat pump only)
means
"High static pressure-Standard".
values are normally somewhat higher during actual operation as a result of ambient conditions.
FXSQ100MVE
10,000
39,600
11.6
11.2
10,800
42,700
12.5
Galvanized Steel Plate
300×1,400×800
3×14×1.75
0.338
3D18H2A
Sirocco Fan
225×1
28/22
107-75
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Glass Fiber
Resin Net (with Mold Resistant)
φ
9.5 (Flare Connection)
φ
15.9 (Flare Connection)
VP25
(External Dia. 32 Internal Dia. 25)
51
43/37
Fuse,
Thermal Protector for Fan Motor
Electronic Expansion Valve
R-410A P Series
BYBS125DJW1
White (10Y9/0.5)
55×1,500×500
6.5
Operation Manual, Installation
Manual, Paper Pattern for Installation,
Drain Hose, Clamp Metal, Insulation
for Fitting, Sealing Pads, Clamps,
Screws, Washers.
3D039431
Specifications
FXSQ125MVE
12,500
49,500
14.5
14.0
13,800
54,600
16.0
Galvanized Steel Plate
300×1,400×800
3×14×1.75
0.338
3D18H2A
Sirocco Fan
225×1
38/28
78-39
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Glass Fiber
Resin Net (with Mold Resistant)
φ
9.5 (Flare Connection)
φ
15.9 (Flare Connection)
VP25
(External Dia. 32 Internal Dia. 25)
52
46/41
Fuse,
Thermal Protector for Fan Motor
Electronic Expansion Valve
R-410A P Series
BYBS125DJW1
White (10Y9/0.5)
55×1,500×500
6.5
Operation Manual, Installation
Manual, Paper Pattern for Installation,
Drain Hose, Clamp Metal, Insulation
for Fitting, Sealing Pads, Clamps,
Screws, Washers.
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3412
cfm=m³/min×35.3
47