3.1.2 RXYQ10PY1~12PY1
Item
Inverter
Compressor
STD 1
STD 2
Fan motor
Electronic expansion valve (Main)
Electronic expansion valve (Subcool)
High pressure
Pressure
switch
protection
Low pressure sensor
Discharge gas temperature
protection
(Discharge pipe thermistor)
Temperature
protection
Inverter fin temperature
protection
(Radiator fin thermistor)
Others
Fuse
Appendix
Name
Symbol
Type
M1C
OC protection
device
Type
M2C
OC protection
device
Type
M3C
OC protection
device
OC protection
M1F
device
Y1E
Y2E
For M1C
S1PH
For M2C
S2PH
For M3C
S3PH
SLNPL
R3T
R1T
F1U
For main PC
board
F2U
For Noise filter
F1U
PC board
List of Electrical and Functional Parts
Model
RXYQ10PY1
JT1GCVDKYR@S
14.7A
JT170G-KYE@T
15.0A
3A
(for General overseas : 1.14A)
Fully closed: 0pls
Fully open: 480pls
Fully closed: 0pls
Fully open: 480pls
+0
OFF: 4.0
MPa
ON: 3.0±0.15MPa
−0.12
+0
OFF: 4.0
MPa
ON: 3.0±0.15MPa
−0.12
OFF: 0.07MPa
OFF: 135°C
OFF: 93°C
250V AC 10A Class B Time-lag 3.15A AC 250V
250V AC 10A Class B Time-lag 3.15A AC 250V
250V AC 5A Class B
RXYQ12PY1
3A
349