Daikin VRV III RXYQ5-54PY1 Service Manual page 109

R-410a heat pump 50hz
Table of Contents

Advertisement

Basic Control
Compressor Step Control (Multi outdoor unit connection is available on the standard connection system)
Compressor operations vary with the following steps according to information in "2.2 Compressor PI Control".
Furthermore, the operating priority of compressors is subject to information in " Operating Priority and Rotation of
Compressors".
Stand-alone installation
RXYQ8PY1
RXYQ5PY1
STEP
STEP
INV
No.
No.
1
1
52 Hz
2
2
56 Hz
3
3
62 Hz
4
4
68 Hz
5
5
74 Hz
6
6
80 Hz
7
7
88 Hz
8
8
96 Hz
9
9
104 Hz
10
10
110 Hz
11
11
116 Hz
12
12
124 Hz
13
13
132 Hz
14
14
144 Hz
15
15
158 Hz
16
16
166 Hz
17
17
176 Hz
18
18
188 Hz
19
20
21
22
23
24
Notes:
1. INV : Inverter compressor
STD1 : Standard compressor 1
STD2 : Standard compressor 2
2. Depending on the operating conditions of compressors, the compressors may run in patterns other than those
aforementioned.
98
RXYQ10PY1, 12PY1
STEP
INV
STD1
INV
No.
1
52 Hz
OFF
52 Hz
2
56 Hz
OFF
56 Hz
3
62 Hz
OFF
62 Hz
4
68 Hz
OFF
68 Hz
5
74 Hz
OFF
74 Hz
6
80 Hz
OFF
80 Hz
7
88 Hz
OFF
88 Hz
8
96 Hz
OFF
96 Hz
9
104 Hz
OFF
104 Hz
10
110 Hz
OFF
110 Hz
11
116 Hz
OFF
116 Hz
12
124 Hz
OFF
124 Hz
13
132 Hz
OFF
132 Hz
14
144 Hz
OFF
144 Hz
15
158 Hz
OFF
158 Hz
16
166 Hz
OFF
166 Hz
17
176 Hz
OFF
176 Hz
18
188 Hz
OFF
188 Hz
19
202 Hz
OFF
202 Hz
20
210 Hz
OFF
210 Hz
21
52 Hz
218 Hz
22
62 Hz
232 Hz
23
68 Hz
248 Hz
24
74 Hz
266 Hz
25
80 Hz
26
88 Hz
27
96 Hz
28
104 Hz
29
116 Hz
30
124 Hz
31
132 Hz
32
144 Hz
33
158 Hz
34
176 Hz
35
188 Hz
36
202 Hz
37
210 Hz
RXYQ14PY1, 16PY1
STEP
INV
STD1
No.
1
52 Hz
OFF
2
56 Hz
OFF
3
62 Hz
OFF
4
68 Hz
OFF
5
74 Hz
OFF
6
80 Hz
OFF
7
88 Hz
OFF
8
96 Hz
OFF
9
104 Hz
OFF
10
110 Hz
OFF
11
116 Hz
OFF
12
124 Hz
OFF
13
132 Hz
OFF
14
144 Hz
OFF
15
158 Hz
OFF
16
166 Hz
OFF
17
176 Hz
OFF
18
188 Hz
OFF
19
202 Hz
OFF
20
210 Hz
OFF
21
52 Hz
ON
ON
22
62 Hz
ON
ON
23
68 Hz
ON
ON
24
74 Hz
ON
ON
25
80 Hz
ON
ON
26
88 Hz
ON
ON
27
96 Hz
ON
ON
28
104 Hz
ON
ON
29
116 Hz
ON
ON
30
124 Hz
ON
ON
31
132 Hz
ON
ON
32
144 Hz
ON
ON
33
158 Hz
ON
ON
34
176 Hz
ON
ON
35
188 Hz
ON
ON
36
202 Hz
ON
ON
37
210 Hz
ON
ON
38
52 Hz
ON
39
62 Hz
ON
40
74 Hz
ON
41
88 Hz
ON
42
96 Hz
ON
43
104 Hz
ON
44
124 Hz
ON
45
144 Hz
ON
46
158 Hz
ON
47
166 Hz
ON
48
176 Hz
ON
49
188 Hz
ON
50
202 Hz
ON
51
210 Hz
ON
RXYQ18PY1
STEP
INV
STD1
STD2
No.
1
52 Hz
OFF
OFF
2
56 Hz
OFF
OFF
3
62 Hz
OFF
OFF
4
68 Hz
OFF
OFF
5
74 Hz
OFF
OFF
6
80 Hz
OFF
OFF
7
88 Hz
OFF
OFF
8
96 Hz
OFF
OFF
9
104 Hz
OFF
OFF
10
110 Hz
OFF
OFF
11
116 Hz
OFF
OFF
12
124 Hz
OFF
OFF
13
132 Hz
OFF
OFF
14
144 Hz
OFF
OFF
15
158 Hz
OFF
OFF
16
166 Hz
OFF
OFF
17
176 Hz
OFF
OFF
18
188 Hz
OFF
OFF
19
202 Hz
OFF
OFF
20
210 Hz
OFF
OFF
21
52 Hz
ON
OFF
22
62 Hz
ON
OFF
23
68 Hz
ON
OFF
24
74 Hz
ON
OFF
25
80 Hz
ON
OFF
26
88 Hz
ON
OFF
27
96 Hz
ON
OFF
28
104 Hz
ON
OFF
29
116 Hz
ON
OFF
30
124 Hz
ON
OFF
31
132 Hz
ON
OFF
32
144 Hz
ON
OFF
33
158 Hz
ON
OFF
34
176 Hz
ON
OFF
35
188 Hz
ON
OFF
36
202 Hz
ON
OFF
37
210 Hz
ON
OFF
38
52 Hz
ON
ON
39
62 Hz
ON
ON
40
74 Hz
ON
ON
41
88 Hz
ON
ON
42
96 Hz
ON
ON
43
104 Hz
ON
ON
44
124 Hz
ON
ON
45
144 Hz
ON
ON
46
158 Hz
ON
ON
47
166 Hz
ON
ON
48
176 Hz
ON
ON
49
188 Hz
ON
ON
50
202 Hz
ON
ON
51
210 Hz
ON
ON
52
218 Hz
ON
53
232 Hz
ON
54
248 Hz
ON
55
266 Hz
ON
Si34-601A
STD2
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
Function

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vrv iii si34 601a rxyq py1

Table of Contents