Reverse Phase, Open Phase; U1" Reverse Phase, Open Phase - Daikin VRV III RXYQ5-54PY1 Service Manual

R-410a heat pump 50hz
Table of Contents

Advertisement

Troubleshooting by Indication on the Remote Controller
3.41 "U1"

Reverse Phase, Open Phase

U1
Remote
Controller
Display
Applicable
RXYQ5P~54P
Models
Method of
The phase of each phase are detected by reverse phase detection circuit and right phase or
reverse phase are judged.
Malfunction
Detection
Malfunction
When a significant phase difference is made between phases.
Decision
Conditions
Supposed
Causes
Troubleshooting
276
Power supply reverse phase
Power supply open phase
Defect of outdoor PC board (A1P)
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
There
is an open phase
at the power supply
terminal section (X1M)
of the outdoor
unit.
NO
Operation
is normal if one
place of power supply
line phase is
replaced.
NO
YES
YES
Si34-601A
Fix the open phase. Requires
inspection of field power supply
section.
Reverse phase
Counter measure of the problem is
completed by phase replacement.
Replace outdoor unit PC board
(A1P).
(V2820)
Troubleshooting