Display "Under Centralized Control" Blinks (Repeats Double Blink) - Daikin VRV III RXYQ5-54PY1 Service Manual

R-410a heat pump 50hz
Table of Contents

Advertisement

Troubleshooting (OP: Unified ON/OFF Controller)
5.3
Display "Under Centralized Control" Blinks (Repeats
Double Blink)
Remote
Controller
Display
Applicable
Unified ON/OFF controller
Models
Method of
Detect the malfunction according to DIII-NET transmission data.
Malfunction
Detection
Malfunction
When no central control addresses are set to indoor units.
When no indoor units are connected within the control range.
Decision
Conditions
Supposed
Causes
Troubleshooting
310
"under centralized control" (Repeats double blink)
Central control address (group No.) is not set for indoor unit.
Improper control range setting switch
Improper wiring of transmission wiring
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
Is the central
control address (group No.)
set for the
indoor unit?
YES
Is the control
range setting switch
set correctly?
YES
Is
the transmission
wiring disconnected or
wired incorrectly?
NO
NO
NO
YES
Si34-601A
Set by remote controller the
central control address for all
indoor units connected to the
central control line.
Set the control range setting
switch correctly and
simultaneously reset the power
supply for all optional controllers
Fix the wiring correctly.
Replace the unified ON/OFF
controller.
Troubleshooting
(V2844)

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vrv iii si34 601a rxyq py1

Table of Contents