Group 5 Multi-Step Speed and PLC Parameters

Pr.
5-00
1st Step Speed Freq.
5-01
2nd Step Speed Freq.
5-02
3rd Step Speed Freq.
5-03
4th Step Speed Freq.
5-04
5th Step Speed Freq.
5-05
6th Step Speed Freq.
5-06
7th Step Speed Freq.
5-07
PLC Mode
5-08
PLC Forward/ Reverse Motion
5-09
Time Duration of Master Speed
5-10
Time Duration of 1st Step Speed
5-11
Time Duration of 2nd Step Speed
5-12
Time Duration of 3rd Step Speed
5-13
Time Duration of 4th Step Speed
5-14
Time Duration of 5th Step Speed
5-15
Time Duration of 6th Step Speed
5-16
Time Duration of 7th Step Speed

Group 6 Protection Parameters

Pr.
6-00
Over-Voltage Stall Prevention
Over-Voltage Stall Prevention Level
6-01
6-02
Over-Current Stall Prevention Level
6-03
Over-Torque Detection Mode
Revision August 2008, SE09, SW V2.61
Explanation
Explanation
Chapter 5 Parameters|VFD-S Series
Settings
d0.0 to d400 Hz
d0.0 to d400 Hz
d0.0 to d400 Hz
d0.0 to d400 Hz
d0.0 to d400 Hz
d0.0 to d400 Hz
d0.0 to d400 Hz
d0: Disable PLC Operation
d1: Execute one program cycle
d2: Continuously execute program
cycles
d3: Execute one program cycle step
by step
d4: Continuously execute one
program cycle step by step
d5: Disable PLC operation, but can
set direction of 1st speed to 7th
speed
d0 to d255 (0: FWD 1: REV)
d0 to d65500 Sec
d0 to d65500 Sec
d0 to d65500 Sec
d0 to d65500 Sec
d0 to d65500 Sec
d0 to d65500 Sec
d0 to d65500 Sec
d0 to d65500 Sec
Settings
d0: Disable
d1: Enable
115V/230V series: d350 to d410V
460V series: d700 to d820V
d20 to d150%
d0: Disabled
d1: Enabled during constant speed
operation. After the over-torque
is detected, keep running until
OL1 or OL occurs.
d2: Enabled during constant speed
operation. After the over-torque
is detected, stop running.
d3: Enabled during running and
continues before Continuous
Output Time Limit (Pr.6-05) is
reached.
Factory
NOTE
Setting
d0.0
d0.0
d0.0
d0.0
d0.0
d0.0
d0.0
d0
d0
d0
d0
d0
d0
d0
d0
d0
d0
Factory
NOTE
Setting
d1
d390
d780
d130
d0
5-7